Inputs and outputs for compressor start and operation

Relay outputs for motor contactors

Terminal strip CN2, terminals 1 and 2

Continuous current max. 2.5 A
Switching voltage 240 V AC
Switching capacity 300 VA, inductive (NC contact: D300, NO contact: C300)

Input signal of safety chain

Terminal strip CN2, terminal 3

115 .. 230 V +10%/-15%, 50/60 Hz

Control circuit fuse (F03): 4 A time-lag at 230 V / 8 A time-lag at 115 V

Output signal of safety chain

Terminal strip CN2, terminal 2

Signal output "collective fault" (P10)

Terminal strip CN2, terminal 4
115 .. 230 V +10%/-15%, 50/60 Hz. max. 2.5 A (C300)

Connection for high pressure switch (B10)

Terminal strip CN3

Terminal 1: output, normally open (NO) contact
Terminal 2: input

Select the operating voltage of the high pressure switch according to the voltage of the safety chain. It must be within the permitted operating voltage range of the compressor module.

Command for compressor as timer start

Terminal strip CN11, terminal 1: input
Terminal strip CN14, terminal 3: output: 24 V DC
Execute the signal of timer start as a normally open (NO) contact.