Inputs and outputs for compressor start and operation
Relay outputs for motor contactors | Terminal strip CN2, terminals 1 and 2 Continuous current max. 2.5 A |
Input signal of safety chain | Terminal strip CN2, terminal 3 115 .. 230 V +10%/-15%, 50/60 Hz Control circuit fuse (F03): 4 A time-lag at 230 V / 8 A time-lag at 115 V |
Output signal of safety chain | Terminal strip CN2, terminal 2 |
Signal output "collective fault" (P10) | Terminal strip CN2, terminal 4 |
Connection for high pressure switch (B10) | Terminal strip CN3 Terminal 1: output, normally open (NO) contact Select the operating voltage of the high pressure switch according to the voltage of the safety chain. It must be within the permitted operating voltage range of the compressor module. |
Command for compressor as timer start | Terminal strip CN11, terminal 1: input |