Setting the communication for compressor start in FI operation

The auxiliary relay K19 "safety chain enabled" is a message from the module to the FI. It releases the FI for compressor operation and activates the STO in case of faults.

The switch-on process of a compressor with FI differs from direct starting methods: The FI will report the cut-in time to the module via the auxiliary relay K18 "FI outputs power voltage/rotating field to motor".

This signal is the start command for important timers of operating and monitoring functions. This is in particular essential for the oil monitoring and oil supply.

  1. Connect the start signal of the superior controller (K01) as normally open (NO) contact to the FI.
    Alternatively, the start signal can also be sent to the module via Modbus and passed on to the FI via the output on terminal strip CN2 terminal 1.
  2. Tap signal for control of auxiliary relay K18 in safety chain before input at terminal strip CN2, terminal 3, and route it via the relay contact "compressor is operating" of the FI.
  3. Connect auxiliary relay K18 also as normally open (NO) contact to terminal strip CN11, terminal 1, and to terminal strip CN14, terminal 3.
  4. Connect auxiliary relay K19 to terminal strip CN2 terminal 2.
  5. Connect auxiliary relay K19 also as normally open (NO) contact to the STO of the FI.