Switching the motor contactors on and off at compressor start

The compressor module controls the activation and deactivation times of the motor contactors.

Part winding motor: The contact at CN2:2 closes 1 s after the start signal. The contact at CN2:1 closes 0.5 s afterwards. Both contacts remain closed until the compressor is shut off.

Star-delta motor: The contact at terminal CN2:2 closes 1 s after the start signal and reopens after further 1.5 s. The contact at terminal CN2:1 closes 1.5 s after the start signal and remains closed until the compressor is shut off.

Motor for direct on-line start: The contact at terminal CN2:2 closes 1 s after the start signal and reopens when the compressor is shut off. The contact at terminal CN2:1 is not used.

The terminal assignment chosen for the module prevents a short-circuit from occurring if the time relay control set in the module does not correspond to the motor used. For setting the time relay control to match the motor, refer to Selecting the motor start function.