Start command for timer

The start signal from the superior controller (K01) must be passed on to the compressor module as a start signal for the timer. This start signal activates the timer for motor contactors Q02, Q03 and Q04 and is necessary for further monitoring functions. This does not apply to operation with FI or soft starter. A different start signal is required for this.

  1. Switch start signal from the superior controller (K01) as normally open (NO) contact and connect it:
    to terminal strip CN11, terminal 1 and to terminal strip CN14, terminal 3.
  2. As an alternative to CN14:3, the start signal can also be connected to CN9:1 or CN7:5 if the selected contact is not assigned. Always switch against a 24 V signal from the compressor module.
  3. The start signal can also be transmitted directly via Modbus to the CM-RC-01.

CM-RC-01 before serial number 815292000504FPXXXXXXXXX (previous version)

  1. In this module version, integrate the start signal from the superior controller (K01) as a make contact in the safety chain in front of the module (path 8).