Schematic wiring diagram for operation with frequency inverter (FI)

In FI operation, all contactors including main contactor and overload protection device can be dispensed with if the FI is equipped with the STO function, Operation with FI (FI with integrated STO): fully equipped compressor for standard refrigerants. Optional peripheral devices: two pressure transmitters, additional fan, RI system and OLM-IQ.

Program the frequency inverter so that the compressor is operated in the permissible frequency range. During commissioning, carefully check the system in the entire frequency range for abnormal vibrations and suppress critical frequencies. Operation with a soft starter is possible in the same way. For further information see online document KT-420.

The output signal of the safety chain is present at terminal CN2:2 labelled K1control.