Integrating the RI system into the refrigeration circuit
1 | Compressor with CM-RC-01, RI injection valve, discharge gas temperature sensor and optional additional fan |
2 | RI injection valve |
3 | Pipeline between liquid line and RI injection valve |
4 | Filter dryer |
5 | Sight glass |
- The RI system requires an additional pipe (3).
- Install the pipe from the liquid line to the RI injection valve (2) on the compressor (1), diam. 10 mm or 3/8".
- First guide this pipeline downwards from a horizontal section of the liquid line. This ensures a bubble-free liquid supply.
- Install filter dryer (4). This protects the RI injection valve and the compressor.
- Sight glass (5) can also be installed. This can be used to visually check whether the liquid refrigerant is bubble-free.
- Insulate the suction gas line.