Integrating the RI system into the refrigeration circuit

Refrigeration circuit with RI system
Refrigeration circuit with RI system

1

Compressor with CM-RC-01, RI injection valve, discharge gas temperature sensor and optional additional fan

2

RI injection valve

3

Pipeline between liquid line and RI injection valve

4

Filter dryer

5

Sight glass

  1. The RI system requires an additional pipe (3).
  1. Install the pipe from the liquid line to the RI injection valve (2) on the compressor (1), diam. 10 mm or 3/8".
  2. First guide this pipeline downwards from a horizontal section of the liquid line. This ensures a bubble-free liquid supply.
  3. Install filter dryer (4). This protects the RI injection valve and the compressor.
  4. Sight glass (5) can also be installed. This can be used to visually check whether the liquid refrigerant is bubble-free.
  5. Insulate the suction gas line.