Reset (external reset)
The module locks out in the event of serious malfunctions, after five equal switch-offs in 24 hours or after any five switch-offs within one hour. In this case, the system must be checked before reset:
- Determine the cause. To do this, evaluate alarm messages from the best software.
- Eliminate the cause(s) of the fault.
- Reset.
- The compressor starts when there is a capacity demand.
The module can be reset in various ways.
- Reset by the superior system controller: With a Modbus command (Control Word).
- Reset with the best software: Click
Resetin the menuAlarms.
All system-related alarms with the exception of the motor temperature monitoring can be reset in this way.