Reset (external reset)

The module locks out in the event of serious malfunctions, after five equal switch-offs in 24 hours or after any five switch-offs within one hour. In this case, the system must be checked before reset:

  1. Determine the cause. To do this, evaluate alarm messages from the best software.
  2. Eliminate the cause(s) of the fault.
  3. Reset.
  1. The compressor starts when there is a capacity demand.

The module can be reset in various ways.

  1. Reset by the superior system controller: With a Modbus command (Control Word).
  2. Reset with the best software: Click Reset in the menu Alarms.

All system-related alarms with the exception of the motor temperature monitoring can be reset in this way.