Compressor cooling

The compressor module switches the additional fan on from a discharge gas temperature of 120°C and off again at 100°C. When the discharge gas temperature reaches 135°C, the RI is initially switched on intermittently, from 140°C it is in continuous operation. As long as RI is active, the compressor can only be operated in the upper part load range. The limit for 4-cylinder compressors is 50% and for 6-cylinder compressors 66%.

In part load range below 50%, the module switches on the additional fan for motor cooling at 90°C discharge gas temperature and off again at 70°C for the 4-cylinder compressors 4FES(H)-3(Y) to 4NE(S)(H)-20(Y). For the 4-cylinder compressors 4JE(H)-13Y to 4FE(H)-35(Y) below 50% and for the 6-cylinder compressors below 33% part load the module switches on the fan at 70°C and off at 50°C. If required, the module activates the additional cooling above these limits.