CRII capacity control
The CM-RC-01 adjusts the capacity of the compressor quasi-steplessly according to the set point of the superior system controller. To do this, it switches the CRII solenoid valves. The minimum possible residual capacity depends on the respective compressor configuration. The set point is transmitted either as an analogue signal to CN13 or via Modbus to CN14.
Compressors, each cylinder bank of which is equipped with a CRII capacity regulator, are thus controlled between full load and 10% part load. These are 4-cylinder compressors with two installed capacity regulators and 6-cylinder compressors with three.
8-cylinder compressors for standard refrigerants can be equipped with a maximum of two capacity regulators. Their control range is then between full load and 50%.
Compressors for transcritical R744 applications can be equipped with a maximum of 2 capacity regulators. The 4-cylinder models can be controlled between full load and 10% part load, the 6-cylinder models between full load and 33% part load.
Operation of the compressor at reduced capacity is only permitted within the part load application limits for the selected refrigerant. For application limits see Bitzer software or Technical Information KT-101 in case of compressors for standard refrigerants and KT-102 for transcritical R744 applications.