Control with compressor module CM-RC-01

The compressor module automatically activates the solenoid valves for capacity control and adjusts compressor capacity virtually steplessly according to the set point of the superior system controller.

The superior system controller transmits the capacity requirement either via Modbus to CN14 or as an analogue signal to CN13. Analogue signals with setpoint characteristics Min .. Max or 0 .. Max are possible. The minimum capacity depends on the compressor configuration (Control concepts and activation of the solenoid valves).