Suspecion of burnt refrigerant in terminal box
The combustion of refrigerant in the terminal box can only happen when several very rare errors occur simultaneously. The probability of this event occurring is extremely low. Combustion of fluorine-based refrigerants can release lethal amounts of toxic gases.
DANGERLife-threatening exhaust gases and residues of combustion!

Life-threatening exhaust gases and residues of combustion!
Sufficiently ventilate the machinery room for at least 2 hours.
Never inhale combustion products.
Use appropriate acid-resistant gloves.
- In case of suspected burnt refrigerant in the terminal box:
- Do not enter the place of installation and ventilate it for at least 2 hours.
- Never inhale combustion products.
- Do not enter the place of installation until the combustion gases have completely escaped. The potentially toxic and corrosive exhaust air must be released into the atmosphere.
- Wear suitable acid-resistant gloves.
- Do not touch moist residues, but allow them to dry because they may contain dissolved toxic substances.
- Have trained staff clean the parts concerned.
- Remove corroded components and dispose of them properly