Cycling rate and minimum running times
Be sure to adhere to the following minimum times:
Compressor | Minimum running time | Cycling rate (minimum start-to-start time) |
|---|---|---|
GSD6, GSU6, GSP6 (Orbit 6) | 2 min | 5 min |
GED8, GSD8, GSU8, GSP8 (Orbit 8) | 3 min | 5 min |
ESH7, ELH7 | 3 min | 5 min |
NOTICE
Risk of motor failure!
Risk of motor failure!
The control logic of the superior system controller must meet the specified requirements in any case.