GSD tandems with FI on the secondary compressor (50 Hz)

In each tandem or trio, one compressor is the primary compressor. This should be the compressor with the lowest displacement in the tandem, because it is the first to receive oil from the BAHT header:

To identify the mounting position which is indicated by "primary" and "secondary compressor", please contact Bitzer for the respective compound assembly drawings.

Orbit tandem compounds with 50 Hz supply frequency (=f (fix)) and frequency inverter on the secondary compressor
f (min.): minimum permitted frequency
f (max.): maximum permitted frequency

Primary compressor

f (fix)

Secondary compressor

f (min.)

f (max.)

GSD80295

50 Hz

GSD80385

39 Hz

75 Hz

GSD80295

50 Hz

GSD80421

35 Hz

75 Hz

GSD80295

50 Hz

GSD80485

35 Hz

75 Hz

GSD80385

50 Hz

GSD80421

46 Hz

75 Hz

GSD80385

50 Hz

GSD80485

40 Hz

75 Hz

GSD80421

50 Hz

GSD80485

44 Hz

75 Hz

GSD60120

50 Hz

GSD60137

44 Hz

75 Hz

GSD60120

50 Hz

GSD60154

40 Hz

75 Hz

GSD60137

50 Hz

GSD60154

45 Hz

75 Hz

GSD60120

50 Hz

GSD60182

35 Hz

75 Hz

GSD60137

50 Hz

GSD60182

39 Hz

75 Hz

GSD60154

50 Hz

GSD60182

43 Hz

75 Hz

GSD60120

50 Hz

GSD60235

35 Hz

75 Hz

GSD60137

50 Hz

GSD60235

35 Hz

75 Hz

GSD60154

50 Hz

GSD60235

35 Hz

75 Hz

GSD60182

50 Hz

GSD60235

40 Hz

75 Hz

GSD60120

50 Hz

GSD80295

50 Hz

75 Hz

GSD60137

50 Hz

GSD80295

50 Hz

75 Hz

GSD60154

50 Hz

GSD80295

50 Hz

75 Hz

GSD60182

50 Hz

GSD80295

50 Hz

75 Hz

GSD60120

50 Hz

GSD80385

44 Hz

75 Hz

GSD60137

50 Hz

GSD80385

46 Hz

75 Hz

GSD60235

50 Hz

GSD80295

50 Hz

75 Hz

GSD60154

50 Hz

GSD80385

48 Hz

75 Hz

GSD60120

50 Hz

GSD80421

45 Hz

75 Hz

GSD60137

50 Hz

GSD80421

45 Hz

75 Hz

GSD60182

50 Hz

GSD80385

50 Hz

75 Hz

GSD60154

50 Hz

GSD80421

44 Hz

75 Hz

GSD60182

50 Hz

GSD80421

47 Hz

75 Hz

GSD60120

50 Hz

GSD80485

35 Hz

75 Hz

GSD60235

50 Hz

GSD80385

50 Hz

75 Hz

GSD60137

50 Hz

GSD80485

36 Hz

75 Hz

GSD60154

50 Hz

GSD80485

38 Hz

75 Hz

GSD60235

50 Hz

GSD80421

50 Hz

75 Hz

GSD60182

50 Hz

GSD80485

42 Hz

75 Hz

GSD60235

50 Hz

GSD80485

47 Hz

75 Hz

GSD60120

50 Hz

GSD60120

50 Hz

75 Hz

GSD60137

50 Hz

GSD60137

50 Hz

75 Hz

GSD60154

50 Hz

GSD60154

50 Hz

75 Hz

GSD60182

50 Hz

GSD60182

50 Hz

75 Hz

GSD60235

50 Hz

GSD60235

50 Hz

75 Hz

GSD80295

50 Hz

GSD80295

50 Hz

75 Hz

GSD80385

50 Hz

GSD80385

50 Hz

75 Hz

GSD80421

50 Hz

GSD80421

50 Hz

75 Hz

GSD80485

50 Hz

GSD80485

50 Hz

75 Hz