GSD tandems with FI on the primary compressor (60 Hz)
In each tandem or trio, one compressor is the primary compressor. This should be the compressor with the lowest displacement in the tandem, because it is the first to receive oil from the BAHT header:
- In case of a vertical BAHT header (ORBIT 6 tandem and trio, mixed tandem), the primary compressor is the compressor connected to the bottom part of the BAHT.
- In case of a horizontal BAHT header (ORBIT 8 tandem), the primary compressor is the compressor connected next to the closed end.
To identify the mounting position which is indicated by "primary" and "secondary compressor", please contact Bitzer for the respective compound assembly drawings.
Primary compressor | f (min.) | f (max.) | Secondary compressor | f (fix) |
|---|---|---|---|---|
GSD80295 | 35 Hz | 75 Hz | GSD80385 | 60 Hz |
GSD80295 | 35 Hz | 75 Hz | GSD80421 | 60 Hz |
GSD80295 | 35 Hz | 75 Hz | GSD80485 | 60 Hz |
GSD80385 | 35 Hz | 65 Hz | GSD80421 | 60 Hz |
GSD80385 | 35 Hz | 75 Hz | GSD80485 | 60 Hz |
GSD80421 | 35 Hz | 69 Hz | GSD80485 | 60 Hz |
GSD60120 | 35 Hz | 68 Hz | GSD60137 | 60 Hz |
GSD60120 | 35 Hz | 75 Hz | GSD60154 | 60 Hz |
GSD60137 | 35 Hz | 67 Hz | GSD60154 | 60 Hz |
GSD60120 | 35 Hz | 75 Hz | GSD60182 | 60 Hz |
GSD60137 | 35 Hz | 75 Hz | GSD60182 | 60 Hz |
GSD60154 | 35 Hz | 70 Hz | GSD60182 | 60 Hz |
GSD60120 | 35 Hz | 75 Hz | GSD60235 | 60 Hz |
GSD60137 | 35 Hz | 75 Hz | GSD60235 | 60 Hz |
GSD60154 | 35 Hz | 75 Hz | GSD60235 | 60 Hz |
GSD60182 | 35 Hz | 75 Hz | GSD60235 | 60 Hz |
GSD60120 | 35 Hz | 60 Hz | GSD80295 | 60 Hz |
GSD60137 | 35 Hz | 60 Hz | GSD80295 | 60 Hz |
GSD60154 | 35 Hz | 60 Hz | GSD80295 | 60 Hz |
GSD60182 | 35 Hz | 60 Hz | GSD80295 | 60 Hz |
GSD60120 | 35 Hz | 75 Hz | GSD80385 | 60 Hz |
GSD60137 | 35 Hz | 75 Hz | GSD80385 | 60 Hz |
GSD60235 | 35 Hz | 60 Hz | GSD80295 | 60 Hz |
GSD60154 | 35 Hz | 75 Hz | GSD80385 | 60 Hz |
GSD60120 | 35 Hz | 75 Hz | GSD80421 | 60 Hz |
GSD60137 | 35 Hz | 75 Hz | GSD80421 | 60 Hz |
GSD60182 | 35 Hz | 65 Hz | GSD80385 | 60 Hz |
GSD60154 | 35 Hz | 75 Hz | GSD80421 | 60 Hz |
GSD60182 | 35 Hz | 75 Hz | GSD80421 | 60 Hz |
GSD60120 | 35 Hz | 75 Hz | GSD80485 | 60 Hz |
GSD60235 | 35 Hz | 60 Hz | GSD80385 | 60 Hz |
GSD60137 | 35 Hz | 75 Hz | GSD80485 | 60 Hz |
GSD60154 | 35 Hz | 75 Hz | GSD80485 | 60 Hz |
GSD60235 | 35 Hz | 65 Hz | GSD80421 | 60 Hz |
GSD60182 | 35 Hz | 75 Hz | GSD80485 | 60 Hz |
GSD60235 | 35 Hz | 70 Hz | GSD80485 | 60 Hz |
GSD60120 | 35 Hz | 60 Hz | GSD60120 | 60 Hz |
GSD60137 | 35 Hz | 60 Hz | GSD60137 | 60 Hz |
GSD60154 | 35 Hz | 60 Hz | GSD60154 | 60 Hz |
GSD60182 | 35 Hz | 60 Hz | GSD60182 | 60 Hz |
GSD60235 | 35 Hz | 60 Hz | GSD60235 | 60 Hz |
GSD80295 | 35 Hz | 60 Hz | GSD80295 | 60 Hz |
GSD80385 | 35 Hz | 60 Hz | GSD80385 | 60 Hz |
GSD80421 | 35 Hz | 60 Hz | GSD80421 | 60 Hz |
GSD80485 | 35 Hz | 60 Hz | GSD80485 | 60 Hz |