General Modbus information

Zoom
Correct Modbus wiring

Shielded twisted pair cable must be used. The shield must only be connected in one end of the bus to avoid unwanted ground current in shielding. However, the shield must be unbroken along the complete bus length, except across galvanic isolated repeater.

Shielding and earth connection
IQ: IQ Module (CM-RC or CM-SW)
FI: frequency inverter

Most controllers, gateways, compressor modules, frequency inverters etc. have no galvanic isolation in the Modbus interface. Therefore:

For more information on Modbus, see documentation in the BEST Software: Choose compressor or device > Documentation > Modbus.