Electrical contacts

Danger of electrical shock!
danger

Danger of electrical shock!

Disconnect supply voltage and secure it against being switched on again!

  1. Transfer cable markings when cutting to length.

Size

Nut

Screw

M4

2 Nm

M5

5 Nm

2.6 Nm

M6

4.8 Nm

M6

6 Nm

14 Nm

M7

7 Nm

M8

4.8 Nm

M8

10 Nm

25 Nm

M10

25 .. 30 Nm

40 Nm ①

M10

30 Nm

40 Nm ①

M12

30 .. 35 Nm

40 Nm ①

M12 (CS.105)

60 Nm ①

M16

85 Nm ①

M6 and M8: 4.8 Nm only valid for scroll compressors
M10: 25 .. 30 Nm with reciprocating compressors, 30 Nm with all other products

①: Mount with a pair of wedge lock washers.

  1. Tighten all screwed connections on terminal plate manually with calibrated torque spanner to indicated torque.
  2. Do not use any pneumatically driven tool.

Cable fixing on terminal strips

Spacing pitch

 

3.81 mm

0.25 Nm

5.08 mm

0.5 Nm

These tightening torques apply with and without cables.

Protective earth conductor at earth terminal strip

Size

 

M5

1.3 Nm

  1. Mount the screwed connection on the terminal strip in this order: cable lug, washer, single-coil spring washer, crosshead screw.

Protective earth conductor for housing cover at module housing bottom

Size

Nut

M6

4 Nm

  1. Mount cable lug with toothed washer.

Protective earth conductor at shield connection plate

Size

Nut

M6

5 Nm

  1. Mount the screwed connection in this order: toothed washer, cable lug, washer, thrust washer, nut.

Protective earth conductor of power connection to CSV.

This power connection is screwed into the head of a threaded rod.

FI current bars at CSV.

Size

 

M10

56 Nm

M12

60 Nm

  1. Mount the screwed connection M10 in this order: screw, pair of wedge lock washers, current bar, FI connection, pair of wedge lock washers, nut.