Application envelope

Introduction

The IQ products CSV, CM-RC-01, CM-RC-02, CM-SW-01 and SE-i1 are featured by an application envelope (= application limit) protection function. It protects the compressor against excessive operating conditions, but allows also to receive warnings via Modbus when coming close to the individual limits.

Exemplary application envelope with legend
Exemplary application envelope with legend

Overview of relevant Modbus registers

Register

Name

Description

Type

12005 (I)

Envelope status

Status of the application envelope protection
0 = Compressor stopped
1 = Compressor starting (envelope protection deactivated for 120 s)
2 = Compressor running within limit (within green dashed line)
3 = Compressor stopping (envelope protection deactivated)
4 = Envelope warning is active
5 = Envelope critical is active
6 = Envelope fault is active
8 = Critical alarm "30-12 Envelope: Compressor would be stopped if faults were enabled" is active
10 = Monitoring deactivated

uint8

12006 (I)

Envelope zone

Zone in which the compressor is currently operating — or, if a fault is active, in which zone the operating point was when the fault was set.
0 = Inside application envelope (within green dashed line)
1 = Low evaporation, low condensation
2 = Low evaporation
3 = Low evaporation, high condensation / high pressure
4 = High condensation / high pressure
5 = High evaporation, high condensation / high pressure
6 = High evaporation
7 = High evaporation, low condensation
8 = Low condensation
10 = Monitoring deactivated

uint8

Application envelope zonesSST: Saturated suction temperature = evaporating temperatureSDT: Saturated discharge temperature = condensing temperature
Application envelope zones
SST: Saturated suction temperature = evaporating temperature
SDT: Saturated discharge temperature = condensing temperature