Overview compressor protection devices

Simplified representation. For details, see the description of the individual protection devices.

For relay current 24 V DC, see also information under Relay versions.

SE-B1

SE-B2

SE-B3

SE-B4

SE-B5

SE-E1

SE-E2

SE-E3

SE-E4

SE-E5

SE-C1

SE-C2

SE-G1

SE-G4

SE-i1

Unit

replaced by

SE-B5, SE-B3, SE-B2

SE-B5, SE-B3

SE-B5

SE-E4

SE-E5

SE-E4

SE-i1

SE-i1

SE-G4

replaces

24 V: SE-B1

SE-B1, SE-B2 115 V, SE-B2 230 V

SE-B1, SE-B2, SE-B3

SE-E1, SE-E3

SE-E2

SE-G1

SE-C1, SE-C2

Winding temp. monitoring

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

Monitoring of single phase failure winding temp.

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

Monitoring of cable short-circuit winding temp.

x

x

x

x

x

x

x

Phase monitoring

x

x

x

x

x

x

x

x

x

x

Oil monitoring

x

x

x

Cycling rate monitoring

 

 

x

x

x

further functions

x

x

x

Version 1 supply voltage

230

230

110 .. 240

110 .. 240

110 .. 240

110 .. 240

24 .. 230

110 .. 240

110 .. 240

110 .. 240

24 .. 230

24 .. 230

115 .. 230

110 .. 240

115 .. 240

V

Version 1 supply voltage tolerance

-15/+10

-15/+10

-10/+10

-15/+10

-10/+10

-10/+10

-25/+10

-10/+10

-10/+10

-10/+10

-15/+10

-15/+10

-15/+10

-10/+10

-10/+10

%

Version 1 supply frequency

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

0 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

Hz

Version 2 supply voltage

115

115

24

24

24

24

24

V

Version 2 supply voltage tolerance

-15/+10

-15/+10

-15/+10

-15/+10

-15/+10

-15/+10

-15/+10

%

Version 2 supply frequency

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

Hz

Version 3 supply voltage

24

24

24

24

V

Version 3 supply voltage tolerance

-20/+20

-20/+20

-20/+20

-20/+20

%

Version 3 supply frequency

0

0

0

0

Hz

Version 4 supply voltage

24

24

V

Version 4 supply voltage tolerance

-15/+10

-15/+10

%

Version 4 supply frequency

50 .. 60

50 .. 60

Hz

Motor voltage

200 .. 600

80 .. 575

600 .. 690

200 .. 690

200 .. 690

83 .. 690

83 .. 690

200 .. 575

200 .. 690

200 .. 690

V

Motor frequency

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

50 .. 60

Hz

designed for soft starter

x

x

x

Max. acceleration time soft starter

2

2

3

s

designed for FI

x

x

x

x

x

Motor voltage FI operation

83 .. 400

83 .. 460

83 .. 460

83 .. 690

V

Motor frequency FI operation

20 .. 100

20 .. 135

20 .. 100

20 .. 100

20 .. 135

Hz

Relay voltage AC

24 .. 250

24 .. 250

24 .. 240

24 .. 250

24 .. 240

24 .. 250

24 .. 240

24 .. 250

24 .. 240

24 .. 240

24 .. 250

24 .. 250

24 .. 250

24 .. 240

24 .. 240

V

Relay voltage DC

min. 24

min. 24

min. 24

min. 24

max. 24

min. 0,1

max. 24

min. 24

V

Relay current

0,02 .. 2,5

0,02 .. 2,5

0,02 .. 2,5

0,02 .. 2,5

0,02 .. 2,5

max. 2,5

0,0005 .. 2,5

max. 2,5

0,02 .. 2,5

0,02 .. 2,5

max. 5

max. 5

max. 2,5

0,02 .. 2,5

0,02 .. 2,5

A

Relay current 24 V DC (var. 3)

max. 0,01

max. 0,01

A

Relay power max.

300

300

300

300

300

300

300

300

300

300

300

300

300

300

300

VA

Relay rating

C300

C300

C300

C300

C300

C300

C300

C300

C300

C300

C300

C300

C300

Approval according to

UL508, EN61010

UL508, EN61010

UL508, EN61010

EN61010

EN/UL 60730, EN61010

UL508, EN61010

UL508, EN61010

EN61010

EN/UL 60730, EN61010

EN/UL 60730, EN61010

UL508, EN61010

EN/UL 60730, EN61010

EN/UL 60730, EN61010

Ambient temp.

-30 .. 70

-30 .. 70

-30 .. 60

-30 .. 60

-30 .. 70

-30 .. 60

-30 .. 70

-30 .. 60

-30 .. 70

-30 .. 70

-30 .. 60

-30 .. 60

-30 .. 60

-30 .. 70

-30 .. 60

°C

Storage temp.

-30 .. 70

°C

Max. altitude

2000

2000

2000

2000

4000

3000

3000

4000

4000

3000

4000

4000

m

Quick acting fuse max.

4

4

4

4

4

4

4

4

4

4

4

4

4

4

4

A

Enclosure class

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP00

IP20

DIN top hat rail 35mm

x

x

x

x

x

x

x

x

x

x

x

6.3 mm fixed connector

x

x

x

Terminal screws

x

x

x

x

x

x

x

x

x

Spring terminals

x

x

x

Height

50

50

50

50

50

79,2

79,2

79,2

80

80

45

45

80,5

80,5

45

mm

Width

68,3

68,3

68,3

68,3

68,3

68,3

68,3

68,3

68,3

68,3

142

142

68,3

68,3

142

mm

Depth

32,5

32,5

32,5

32,5

32,5

32,5

32,5

32,5

32,5

32,5

90

90

32,5

32,5

90

mm

Cable length winding temp. protection

120

350

350

350

350

mm

Cable length phase monitoring

300

300

300

300

300

300

300

300

300

300

mm