Druck- und Sattdampftemperaturtabelle für R744
Sattdampftemperatur tsat (°C) | Absolutdruck p (bar) |
|---|---|
31,06** ① | 73,84 |
31 | 73,74 |
30 | 72,05 |
29 | 70,42 |
28 | 68,82 |
27 | 67,27 |
26 | 65,74 |
25 | 64,25 |
24 | 62,79 |
23 | 61,36 |
22 | 59,95 |
21 | 58,57 |
20 | 57,22 |
19 | 55,89 |
18 | 54,58 |
17 | 53,30 |
16 | 52,05 |
15 | 50,81 |
14 | 49,60 |
13 | 48,41 |
12 | 47,24 |
11 | 46,10 |
10 | 44,57 |
9 | 43,87 |
8 | 42,78 |
7 | 41,70 |
6 | 40,67 |
5 | 39,65 |
4 | 38,64 |
3 | 37,66 |
2 | 36,69 |
1 | 35,74 |
0 | 34,81 |
-1 | 33,90 |
-2 | 33,00 |
-3 | 32,12 |
-4 | 31,26 |
-5 | 30,42 |
-6 | 29,59 |
-7 | 28,78 |
-8 | 27,99 |
-9 | 27,21 |
-10 | 26,45 |
-11 | 25,71 |
-12 | 24,98 |
-13 | 24,26 |
-14 | 23,56 |
-15 | 22,88 |
-16 | 22,21 |
-17 | 21,55 |
-18 | 20,91 |
-19 | 20,28 |
-20 | 19,67 |
-21 | 19,07 |
-22 | 18,49 |
-23 | 17,91 |
-24 | 17,35 |
-25 | 16,81 |
-26 | 16,27 |
-27 | 15,75 |
-28 | 15,25 |
-29 | 14,75 |
-30 | 14,26 |
-31 | 13,79 |
-32 | 13,33 |
-33 | 12,88 |
-34 | 12,44 |
-35 | 12,02 |
-36 | 11,60 |
-37 | 11,19 |
-38 | 10,80 |
-39 | 10,42 |
-40 | 10,04 |
-41 | 9,68 |
-42 | 9,32 |
-43 | 8,98 |
-44 | 8,64 |
-45 | 8,32 |
-46 | 8,00 |
-47 | 7,70 |
-48 | 7,40 |
-49 | 7,11 |
-50 | 6,83 |
-51 | 6,55 |
-52 | 6,29 |
-53 | 6,03 |
-54 | 5,78 |
-55 | 5,54 |
-56 | 5,31 |
① Kritischer Punkt