Compressor and accessories

This chapter describes the additional residual risks posed by the condensing compressor when using A3 safety group refrigerants and provides explanations. This information helps the system manufacturer carry out the required risk assessment of the system. The information alone can in no way replace the risk assessment for the system.

Design, maintenance and operation of refrigeration systems using flammable refrigerants of the safety group A3 are subject to particular safety regulations.

When installed according to the Operating Instructions, the compressors for R290 and R1270, including the fitted accessories, are, in normal operation without malfunction, free of ignition sources that may ignite the flammable refrigerants. They are considered technically tight. In their basic version, the compressors and, if applicable, the additional fan must not be operated in an ignitable atmosphere. Operation in an Ex zone requires special Ex designs that include a suitable electrical system and approval.

The separately supplied components, such as additional fan and compressor protection device, are not free of ignition sources. They must not be operated in an ignitable atmosphere.

The following description includes only components affected by the safety regulations. Otherwise, the above-mentioned regulations shall apply.

It is imperative to guarantee the enclosure class of the electrical terminal box and electrical accessories!

It is imperative to guarantee the enclosure class of the electrical terminal box and electrical accessories!

Execute the cable bushings with maximum care using only the sealing elements suitable for this purpose!

The protection device is delivered in each case as a separately packaged item and must be installed in the switch cabinet or a separate terminal box.

Schematic wiring diagrams for the connection of the compressor protection devices can be found in the Technical Information AT-300 (HTML).

Connect the protection device as specified in the schematic wiring diagram.

Connect the protection device as specified in the schematic wiring diagram.

Danger of induction! Use only shielded cables for the connecting lines (PTC control circuit) between terminals 1/2 (SE-B* and SE-E*) and 3/4 (terminal plate). Connect the discharge gas temperature sensor in series with terminals 3/4.

When installing the protection devices for screw compressors and scroll compressors in the switch cabinet, observe the following:

Risk of compressor failure!

Risk of compressor failure!

Operate the compressor only in the intended rotation direction!