Oils for refrigerant R717

Bitzer reciprocating compressors for R717 are supplied filled with Reniso KC68 mineral oil or optionally with SHC226E poly-alpha-olefin oi las standard.

BITZER OS. compressors for R717 are supplied as standard without oil.

The following oils are available separately:

Positive experiences have been made with the following oils, among others:

Reniso UltraCool 68 shows very good overall properties (a very good cold flow behaviour, good compatibility with common sealing materials, low evaporation losses) and is therefore recommended as a standard oil for applications with R717.

Technical data

Technical data of the oils for refrigerant R717

Reniso KM32

Reniso KS46

Reniso KC68

Reflo 68A

Reniso
UltraCool 68

SHC226E

Unit

MO

MO

PAO / SC

PAO

Density at 15°C

0.881

0.894

0.894

0.866

0,854

0.830

g/ml

Flashpoint

202

204

223

236

250

250

°C

Pour point

-45

-42

-39

-42

-48

-45

°C

Kinematic viscosity

at 40°C

32

46

68

58

62

67

cSt

at 100°C

4.9

5.8

7.2

7.9

9.1

10.1

cSt

Specific heat capacity

at 40°C

1.95

1.94

1.93

1.96

2,07

2.16

kJ/kg*K

at 100°C

2.17

2.16

2.17

2.17

2,28

2.38

kJ/kg*K

Thermal conductivity

at 40°C

0.13

0.13

0.12

0.13

0,14

0.14

W/m*K

at 100°C

0.13

0.13

0.12

0.13

0,14

0.14

W/m*K

Food safety

NSF-
Certification

H2 ②

H2 ②

H2 ②

H1 ①

① NSF H1 certification: Lubricant suitable for the food industry. Approved for "incidental food contact".

② NSF H2 certification: General lubricant in the food industry. The use of which excludes direct contact with food.

Material safety data sheets

Apart from this document, please observe the material safety data sheet (MSDS) for the respective oil. It contains information on toxicity, handling, personal protective equipment and disposal of the oil. Material safety data sheets for all Bitzer oils are available on request.

Warning values for used oils

The listed oils are categorized as group KAA according to DIN51503, Part 1. To determine the used condition of the oil, e.g. with respect to water content or kinematic viscosity, the reference values of DIN 51503, Part 2, apply. The visual assessment (oil sample from the low pressure side) is also decisive: clear oil in the colour of fresh oil and without solid components is generally still usable. If the oil is noticeably darker than fresh oil, the water content in particular should be checked.

Warning values for used oils for the refrigerant R717.
(*): that is ± 15% of the value for new oil. According to the standard, larger deviations in the direction of a higher viscosity are permissible,

Oil

Kinematic viscosity at 40°C (DIN EN ISO3104)

Max. water content (DIN51777)

Total acid number
(DIN ISO6618)

Reniso KM32

outside of 27 .. 37 cSt (*)

100 mg H2O/‍kg oil

0.3 mg KOH/g

Reniso KS46

outside of 39 .. 53 cSt (*)

100 mg H2O/‍kg oil

0.3 mg KOH/g

Reniso KC68

outside of 58 .. 78 cSt (*)

100 mg H2O/‍kg oil

0.3 mg KOH/g

Reflo 68A

outside of 49 .. 67 cSt (*)

100 mg H2O/‍kg oil

0.3 mg KOH/g

Reniso UltraCool 68

outside of 53 .. 71 cSt (*)

100 mg H2O/‍kg oil

0.3 mg KOH/g

SHC226E

outside of 57 .. 77 cSt (*)

100 mg H2O/‍kg oil

0.3 mg KOH/g

Elastomer compatibility

Mineral oils or poly-alpha-olefin oil with seal conditioner with refrigerant R717:

Recommended seaI materials:

Poly-alpha-olefins with refrigerant R717:

Relevant literature recommends the following seaI material: