Retrofit to A2L in no or limited ex-zone

Example task: An existing small refrigeration system has to be retrofitted from R404A to the A2L flammable refrigerant R454C. An Ex zone should be avoided as far as possible.

A2L refrigerant can only be used in existing systems, where safety standards and local regulations allow this. The necessary safety measures have to be taken. This can in some cases be sufficient room size, sufficient ventilation or a gas warning system shutting down the electrics in the sensitive area and giving alarm inside and outside the room. This risk evaluation has to be done before the retrofit!

A2L refrigerant can only be used in existing systems, where safety standards and local regulations allow this.

The necessary safety measures have to be taken. This can in some cases be sufficient room size, sufficient ventilation or a gas warning system shutting down the electrics in the sensitive area and giving alarm inside and outside the room.

This risk evaluation has to be done before the retrofit!

Special tools or preconditions:

Working steps or preconditions:

  1. Educated worker
  2. Check compatibility of parts with new refrigerant A2L
  3. a. doublecheck with parts manufacturers or their documentation/apps
  4. Read / inform for risk assessment of system
  5. Check ventilation of site or room, A2L ready?
  6. Check location of main switch
  7. Have A2L fire extinguisher ready
  8. Put warning sign to notify work in progress, especially where refrigerant might be released
  9. Power off compressor / system
  10. Leak test system with R404A sniffer
  11. Pump down system and compressor
  12. Remove R404A with recovery machine to the lowest possible limit (residual R404A at very low level can stay in the system)
  13. Oil heater on
  14. Exchange oil, if miscoloured
  15. Evacuate system
  16. Exchange parts necessary
  17. Tightness test with dry nitrogen
  18. Test pressure switches
  19. a. Set low pressure cut out to avoid operation in vacuum
  20. Evacuate system
  21. Start charging the system with A2L refrigerant
  22. a. Now have a A2L gas detector with you and ventilation on
  23. Sticker for flammable gas on compressor and system
  24. Put sticker on technical room door
  25. Update the system log book with new refrigerant and charge
  26. a. Add new pressure switch settings
  27. Update system operating instructions with new refrigerant
  28. Update risk assessment for operation with A2L refrigerant

More details on retrofit procedure and material compatibility: