Necessary preparations before retrofit of R404A/R507A to R448A/R449A
- The conversion changes the maximum allowable pressure, and depending on the operating conditions and system design probably also the refrigerating capacity.
- Before a refrigeration system can be retrofitted from a current to a new refrigerant, the present status is to be determined. During this, the opportunity to eliminate leaks and malfunctions should be used. Following this, the components and the layout are checked for compatibility with the new refrigerant. Amongst others, the following is to be noted:
Design operating conditions or application range, like medium temperature or low temperature refrigeration, ... |
Year of establishment. |
Refrigerating capacity at design operating conditions. |
Current refrigerating capacity demand at design operating conditions: |
Current refrigerant. |
Compressor:
|
Expansion devices:
|
Solenoid valves:
|
Pressure controls:
|
Filter drier:
|
Heat exchangers (evaporators, condensers, desuperheaters, internal heat exchangers, ...):
|
Oil:
|
Visible damages, dirt aso. |
- Before retrofitting, it should be checked whether the refrigerant change touches safety or approval rules, where the documentation maybe lists specific refrigerants.
- Data for components and materials are to be provided to show whether they can be used further on.
- If this is not possible to get, new components and materials are to be purchased, that are suitable for the new refrigerant.
New refrigerant (Refrigerant comparison to R404A/R507A). |
New refrigerant stickers. |
Oil:
|
Compressor:
|
Expansion devices:
|
Solenoid valves:
|
Filter drier:
|
Pressure controls:
|
For screw compressors the necessity to install or enlarge the oil cooler is checked. Calculations are done with the BITZER SOFTWARE. |
Bottles for disposal or recycling of refrigerant. |
Container/bottles for disposal of oil. |
Availability of appropriate tools and test equipment. |