Solutions by BITZER for future refrigerants

Refrigerating capacity of low GWP refrigerants in BITZER reciprocating compressors (medium temperature range)

Refrigerating capacity of low GWP refrigerants in BITZER reciprocating compressors (medium temperature range)
Refrigerating capacity of low GWP refrigerants in BITZER reciprocating compressors (medium temperature range)

Rating points according to EN12900, evaporating temperature: -10°C

➀ screw compressors

Refrigerating capacity of low GWP refrigerants in BITZER reciprocating compressors (low temperature refrigeration range)

Refrigerating capacity of low GWP refrigerants in BITZER reciprocating compressors (low temperature refrigeration range)
Refrigerating capacity of low GWP refrigerants in BITZER reciprocating compressors (low temperature refrigeration range)

Rating points according to EN12900, evaporating temperature: -35°C

➀ screw compressors

 

Refrigerant blends

The new refrigerants will mostly be blends of known and new substances. HFCs (hydro fluoro carbons) are known substances, the new ones include so-called HFOs, i.e. HFC with unsaturated carbon-carbon-bonds. Partly HCs (hydro carbons) will be used in the mixtures.

Most refrigerant mixtures with lower GWP contain components listed in the following table. These listed components are known and tested for compatibility by BITZER. For many refrigerants, performance data is available in the BITZER SOFTWARE or by request.

Common refrigerant mixture components

Type

Refrigerant

GWP

Safety class

Material/Oil

HFC

R32

675

A2L

known

R125

3500

A1

known

R134a

1430

A1

known

R143a

4470

A2

known

R152a

124

A2

known

R227ea

3220

A1

known

HFC unsaturated

R1234yf

4

A2L

known

R1234ze(E)

6

A2L

known

HC

R290

3

A3

known

R600

3

A3

known

R600a

3

A3

known

R1270

2

A3

known

CO2

R744

1

A1

known

Products

For mixtures unlisted in the BITZER Software or brochures, the following applies: If only components listed in the above table are used in the mixtures, and the vapour pressure curves are not below that of R134a and not above that of R404A or R407F, the following BITZER product ranges can be used in field test installations:

Application

Many new refrigerant mixtures, targeting replacement of R404A or R22, have a significant temperature glide of 4 .. 7 K or even more, during both evaporation and condensation. Depending on the system and heat exchanger design, this can lead to different evaporation and condensing temperatures than with e.g. R404A. Thus the operating conditions of the compressor can change, resulting in need for additional cooling earlier than would expected by the comparison of theoretical data.

Application limits

Application limits for R134a, R404A, R407A, R407F, R448A, R449A, R450A, R513A, R1234yf and R1234ze(E) can be found in the BITZER Software and the corresponding product brochures.

The application limits of R134a can be used as a guideline for refrigerants having similar pressure, if no specific ones are listed. The application limits of R407A can be used as a guideline for refrigerants with similar pressures as R404A or R407F.

Additional limitations can apply due to discharge temperatures at high pressure ratio.

Flammability classification

If the refrigerant material or mixture to be used is listed as flammable – A3, A2 or A2L according to ASHRAE 34, ISO817 resp. EN378-1 – the system installation is to be made safe for the use of flammable refrigerants according to local regulations. For the compressors, BITZER strongly recommends to place the motor protection device in the switch cabinet (not in the terminal box), if not otherwise documented.

In the EU, a risk assessment according to the EU Explosion Protection Directive 2014/34/EU might be necessary. The preferred method to comply with regulations is to avoid a flammable concentration by appropriate measures. When planning use of a flammable refrigerant not allowed in the technical documentation, please contact BITZER.

See also:

Flammability and GWP correlations

to be replaced

Properties of potential alternative refrigerants

GWP

T-glide

Group

R134a

550 .. 660

< 1 K

A1

4 .. 150

0 K

A2L

R404A

1500 .. 2100
(without HFO)

< 7 K

A1

1000 .. 1400

< 4 K

A1

approx. 250

?

A2L

approx. 150

?

A2L/A2