ECOLINE SL / ME subcritical

All connections to the pipes are made of steel.

R744 is an odourless and colourless gas and cannot be perceived directly in case of emission!

R744 is an odourless and colourless gas and cannot be perceived directly in case of emission!

Lost of consciousness and danger of suffocation by inhaling higher concentrations!

Avoid R744 emission and uncontrolled deflating, particularly in closed rooms!

Aerate closed machine rooms!

Comply with safety regulations in accordance with national legislation and applicable standards, e. g. EN 378, DIN EN ISO5149 and DIN EN ISO24664!

Liquid R744 evaporates quickly, cools down at the same time and forms dry ice!
danger

Liquid R744 evaporates quickly, cools down at the same time and forms dry ice!

Danger of cold burns and frost bites!

Avoid uncontrolled deflating of R744!

When filling the system with R744, wear gloves and goggles!

In addition to the safety references listed in this document, it is essential to observe the references and residual risks in the respective operating instructions!

ECOLINE SL

Shut-off valves for R744 compressors, subcritical application (SL models).
For most compressors there is only one listed standard valve (in contrast to e.g. compressors for transcritical application).
Ø: diameter
HP: high pressure
LP: low pressure

Compressor

Side

Connection at compressor

Valve

Ø of suitable brazing pipes

Ø of suitable welding pipes

2NSL .. 2FSL

HP

12 mm // 1/2''

Di12/Da17

1/2''

17.2 mm (DN10)

LP

16 mm // 5/8''

Di16/Da22

5/8'' // 16 mm

21.3 mm (DN15)

2ESL .. 2CSL

HP

16 mm // 5/8''

Di16/Da22

5/8'' // 16 mm

21.3 mm (DN15)

LP

22 mm // 7/8''

Di22/Da30

7/8'' // 22 mm

26.9 mm (DN20)

4DSL .. 4CSL

HP

22 mm // 7/8''

Di22/Da30

7/8'' // 22 mm

26.9 mm (DN20)

LP

28 mm // 1 1/8''

Di28/Da35/RL

1 1/8''

33.7 mm (DN25)

4FSL .. 4ESL

HP

16 mm // 5/8''

Di16/Da22

5/8'' // 16 mm

21.3 mm (DN15)

LP

28 mm // 1 1/8''

Di28/Da35/RL

1 1/8''

33.7 mm (DN25)

4VSL

HP

22 mm // 7/8''

Di22/Da30

7/8'' // 22 mm

26.9 mm (DN20)

LP

35 mm // 1 3/8''

Di35/Da42
Di35/Da42/UL

1 3/8'' // 35 mm

42.4 mm (DN32)

4TSL .. 4NSL

HP

28 mm // 1 1/8''

Di28/Da35/TX

1 1/8''

33.7 mm (DN25)

LP

35 mm // 1 3/8''

Di35/Da42
Di35/Da42/UL

1 3/8'' // 35 mm

42.4 mm (DN32)

ECOLINE ME

Shut-off valves for R744 compressors, subcritical application with high standstill pressure (ME models).
For some compressors there is only one listed standard valve (in contrast to e.g. compressors for transcritical application).
Ø: diameter
HP: high pressure
LP: low pressure

Compressor

Side

Connection at compressor

Valve

Ø of suitable brazing pipes

Ø of suitable welding pipes

2MME .. 2FME

HP

12 mm // 1/2''

Standard: Di12/Da17/TX
Option: Di12/Da17/TT

1/2''

17.2 mm (DN10)

LP

16 mm // 5/8''

Di16/Da22

5/8'' // 16 mm

21.3 mm (DN15)

2EME .. 2DME

HP

16 mm // 5/8''

Standard: Di16/Da22/TX
Option: Di16/Da22/TT

5/8'' // 16 mm

21.3 mm (DN15)

LP

22 mm // 7/8''

Di22/Da30

7/8'' // 22 mm

26.9 mm (DN20)

4DME

HP

22 mm // 7/8''

Standard: Di22/Da30/TX
Option: Di22/Da30/TT
Option: Di16/Da22/TT

7/8'' // 22 mm

26.9 mm (DN20)

LP

28 mm // 1 1/8''

Di28/Da35

1 1/8''

33.7 mm (DN25)

4FME(M) .. 4EME(M)

HP

16 mm // 5/8''

Standard: Di16/Da22/TX
Option: Di22/Da30/TT
Option: Di16/Da22/TT

5/8'' // 16 mm

21.3 mm (DN15)

LP

28 mm // 1 1/8''

Di28/Da35

1 1/8''

33.7 mm (DN25)

4TME(M) .. 4PME(M)

HP

28 mm // 1 1/8''

Standard: Di28/Da35/TX
Option: Di28/Da35/TT

1 1/8''

33.7 mm (DN25)

LP

35 mm // 1 3/8''

Standard: Di35/Da42/TX
Option: Di35/Da42/TT

1 3/8'' // 35 mm

42.4 mm (DN32)

6TME(M) .. 6PME(M)

HP

35 mm // 1 3/8''

Di35/Da42

1 3/8'' // 35 mm

42.4 mm (DN32)

LP

42 mm // 1 5/8''

Di41/Da48

1 5/8''

48.3 mm (DN40)

8VME .. 8PME

HP

DN50

Di54/Da60

2 1/8'' // 54 mm

60.3 mm (DN50)

LP

DN65

Standard: Di68/Da76
Option: Blind flange

2 5/8''

76.1 mm (DN65)

Nominal diameters (DN) are not actual dimensions!

Nominal diameters (DN) are not actual dimensions!

The nominal diameters DN10 .. DN200 only indicate ranges! The number is not a quantifiable unit, it is only indirectly related to the diameters of the connections and should not be used in calculations.