Components of wiring diagrams
Components without further terminal strips
F3: Control circuit fuse
F4: Oil heater fuse
K1: Main contactor
M1: Compressor
N1: Frequency inverter (FI)
Q1: Main switch
T1: Transformer
Components containing terminal strips
B1: Controller |
|
|
|
|---|---|---|---|
direkt integriert | 2x Mini-B-USB | data connection | |
RS485 | Modbus connection | ||
RJ45 | Ethernet connection | ||
Bluetooth | data connection | ||
H4 | integrated display | ||
CN5 | R3 | 5, 6 | discharge gas temperature sensor |
R4 | 2, 3 | ambient temperature sensor | |
CN6 | R8 | 2, 3 | suction gas temperature sensor |
CN7 | H1 | 1, 4, 5, 6 | external display (data connection at CN3) |
CN11 | B3 | 4, 5, 6 | high pressure transmitter |
B4 | 1, 2, 3 | low pressure transmitter | |
CN12 | S5 | 1, 3 | potential-free contact for DI1 |
S6 | 2, 6 | potential-free contact for DI2 | |
CN13 | status message (potential-free) | ||
H2 | 2, 1 | signal light: ready-to-operate | |
H3 | 3, 1 | signal light: fault | |
CN15 | H1 | 1, 2 | external display (voltage supply at CN1) |
K5: Relay module |
|
|
|
|---|---|---|---|
CN22 | F1 | 1 | fuse of fan 1 |
F2 | 3 | fuse of fan 2 |
Terminal strip X101 | Component | Terminal | Designation |
|---|---|---|---|
X101 | SE-B* | 5, 6, 7, 8 | compressor protection device |
Delta-PII | 17, 18, 19, 20, 21, 22 | oil pressure monitoring | |
OLC-K1 | 17, 18, 19, 20, 21, 22 | oil level monitoring | |
F5 | 9, 10 (PE) | high pressure switch | |
F6 | 11, 12 | low pressure limiter | |
M2 | 27, 28, 29, 30, PE | fan 1 (supply/aarm) | |
M3 | 23, 24, 25, 26, PE | fan 2 (supply/alarm) | |
R6 | 15, 16 | oil heater | |
S2 | 1, 2 | external release | |
Y1 | 3, 4 | solenoid valve in liquid line | |
Y2 | 14, 13 | RI solenoid valve (refrigerant injection) |
Terminal strip X102 | Component | Terminal | Designation |
|---|---|---|---|
X102 | M2 | 6, 7, 8, 15, 16 | fan 1 (set point/BUS) |
M3 | 4, 5, 12, 13, 14 | fan 2 (set point/BUS) | |
R1, R2 | resistors | ||
R5 | 3, 11 | sensor for cold store temperature | |
K1 | compressor contactor |