Introduction to on site risk assessment

The risk assessment is a tool to enable safe work. The main questions driving it are thus

A risk assessment consist basically of the following steps

The risks have to be determined and evaluated for the specific work to be done. For details on risk evaluations please consult specific literature or attend seminars on this topic.

Examples of important risks during maintenance and repair on refrigeration systems with A2L refrigerants in a simplified presentation

Risk

Evaluation

Measure

New
Evaluation

Remark

Work on system with flammable, pressurized and liquified gas

high

Worker has to be skilled and educated in handling the gas, also flammable

low

Unidentified risks from refrigeration system or other parts in the surrounding

high

Ask for system and system use risk assessment. If not available, make own assessment. If not possible, stop the work

low

Worker has to get introduced to existing risk evaluation of system and surrounding. Residual risks should be in system operating instructions and work procedure descriptions

Ignition of refrigerant inside system

middle

Avoid having A2L refrigerant and air mixed in the system or its parts

Evacuation of air and flushing with nitrogen

Ignition of refrigerant coming out during connection of hoses

low

Careful work when connecting hoses

Ignition of refrigerant coming out of system during work on open system

middle

Close valves to this part. Check for leak of the valves. Flush part with nitrogen

Use also mobile gas detector

Ignition of refrigerant coming out of larger leak

high

Identify leak location. Shut off electric power in this area. Shut off this part with valves. Ventilate until concentration is uncritical

Use also mobile gas detector

Ignition of refrigerant coming out of sudden larger leak

middle

Work with tools, that are not able to ignite A2L refrigerant

Have a fire extinguisher as backup

Ignition of refrigerant in areas, where refrigerant is released or ventilated to

high

Set up warning signs in these areas. Do not release to areas with ignition sources

low

Ignition of refrigerant when opening connections with a torch

high

Worker has to be skilled and educated. Pipes containing refrigerant, maybe in oil residues, shall only be opened with a tool without flame

low

Typical risk evaluation schematic