Complete table with filter function
In the following table refrigerants can be selected and compared with the help of filters. To ease the typical search, some extra columns are introduced for filtering:
- Substitute for R134a, R404A, R22, R410A
- Global warming potential range ≤ 150, > 150 .. 750, > 750 .. 2500, > 2500
- Temperature glide range 0, > 0 .. 4 K, > 4 .. 8 K, > 8 K
Data for the most of the listed refrigerants can also be found in the BITZER RefRuler App.
Refrigerant | R134a similar | R404A similar | R22 similar | R410A similar | GWP range | Temp. glide range | Chemical | Group | Components | Name | Manufacturer | Substitute for | Application max (°C) | Application min (°C) | Appl. limitations max (°C) | Appl. limitations min (°C) | Appl. 2-stage max (°C) | Appl. 2-stage min (°C) | ODP | GWP AR4 | GWP AR5 | GWP AR6 | Safety class | Pract. limit AEL (kg/m³) | Molar mass | Normal boiling point (°C) | Normal dew point (°C) | Temperature glide (K) | Crit. temp. (°C) | Crit. pressure (bar) | Cond. temp. at 26 bar abs (°C) | Cond. temp. at 40 bar abs (°C) | Relative refr. capacity (%) | Discharge temp. increase (K) | Oil 1 | Oil 2 | Oil 3 | Oil with limitations 1 | Oil with limitations 2 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
R11 | >2500 | 0 | CCl3F | CFC | trichloro-fluoro-methane | 30 | 0 | 1 | 4750 | 4660 | 5560 | A1 | 0,3 | 137,37 | 23,8 | 23,8 | 0 | 198 | 44,1 | 163 | MO | AB | |||||||||||||||||
R12 | R134a | >2500 | 0 | CCl2F2 | CFC | dichloro-difluoro-methane | 20 | -30 | 1 | 10900 | 10200 | 11200 | A1 | 0,5 | 120,91 | -29,8 | -29,8 | 0 | 112 | 41,2 | 86 | MO | AB | ||||||||||||||||
R13 | >2500 | 0 | CClF3 | CFC | chloro-trifluoro-methane | -30 | -80 | 1 | 14400 | 13900 | 16200 | A1 | 0,5 | 104,46 | -81,4 | -81,4 | 0 | 29 | 38,7 | 11 | MO | AB | |||||||||||||||||
R13B1 | >2500 | 0 | CBrF3 | Halon | trifluoro-bromo-methane | -10 | -60 | 10 | 7140 | 6290 | 7200 | A1 | 0,6 | 148,92 | -57,7 | -57,7 | 0 | 67 | 39,9 | 46 | MO | AB | |||||||||||||||||
R13I1 | ≤150 | 0 | CF3I | IFC | trifluoro-iodo-methane | 0,01 | 1 | 1 | A1 | 195,91 | -21,9 | -21,9 | 0 | 123 | 39,5 | 99 | POE | ||||||||||||||||||||||
R14 | >2500 | 0 | CF4 | PFC | tetrafluoro-methane | -90 | -125 | 0 | 7390 | 6630 | 7380 | A1 | 0,4 | 88,01 | -127,9 | -127,9 | 0 | -46 | 37,5 | -58 | POE | ||||||||||||||||||
R22 | R22 | >750..2500 | 0 | CHClF2 | HCFC | chloro-difluoro-methane | R502, R12 | 12 | -45 | -20 | -50 | 0,055 | 1810 | 1760 | 1960 | A1 | 0,3 | 86,47 | -40,7 | -40,7 | 0 | 96 | 49,9 | 63 | 80 (L) | 35 | MO | AB | |||||||||||
R23 | >2500 | 0 | CHF3 | HFC | trifluoro-methane | R13, R503 | -50 | -95 | 0 | 14800 | 12400 | 14600 | A1 | 0,68 | 70,01 | -82 | -82 | 0 | 26 | 48,3 | 2 | POE | PVE | AB | |||||||||||||||
R32 | R410A | >150..750 | 0 | CH2F2 | HFC | difluoro-methane | R410A | 15 | -15 | 0 | 675 | 677 | 771 | A2L | 0,061 | 52,02 | -51,7 | -51,7 | 0 | 78 | 57,8 | 42 | 61 | 108 (H) | 21 | POE | PVE | AB | |||||||||||
R40 | ≤150 | 0 | CClH3 | ClC | methyl chloride | 20 | -20 | 0,02 | 13 | 12 | 5,54 | B2 | 50,48 | -23,8 | -23,8 | 0 | 143 | 66,8 | MO | ||||||||||||||||||||
R113 | >2500 | 0 | CFCl2CF2Cl | CFC | trichloro-trifluoro-ethane | 0,8 | 6130 | 5820 | 6520 | A1 | 187,38 | 47,6 | 47,6 | 0 | 214,05 | 34,15 | 196 | MO | AB | ||||||||||||||||||||
R114 | >2500 | 0 | CF2ClCF2Cl | CFC | dichloro-tetrafluoro-ethane | 1 | 10000 | 8590 | 9430 | A1 | 170,93 | 3,6 | 3,6 | 0 | 145,7 | 32,63 | 132 | MO | AB | ||||||||||||||||||||
R115 | >2500 | 0 | CF3CF2Cl | CFC | chloro-pentafluoro-ethane | 0,44 | 7370 | 7670 | 9600 | A1 | 154,47 | -39,2 | -39,2 | 0 | 79,95 | 31,29 | 71 | MO | AB | ||||||||||||||||||||
R116 | >2500 | 0 | CF3CF3 | PFC | hexafluoro-ethane | 0 | 12200 | 11100 | 12400 | A1 | 138,01 | -78,1 | -78,1 | 0 | 19,88 | 30,48 | 14 | POE | AB | ||||||||||||||||||||
R123 | ≤150 | 0 | CClF2CClFH | HCFC | dichloro-trifluoro-ethane | R11 | 20 | 0 | 0,02 | 77 | 79 | 90,4 | B1 | 0,1 | 152,92 | 27,8 | 27,8 | 0 | 184 | 36,6 | 163 | MO | AB | ||||||||||||||||
R124 | >150..750 | 0 | CHClFCF3 | HCFC | chloro-tetrafluoro-ethane | R114, R12B1 | 40 | 5 | 0,022 | 609 | 527 | 597 | A1 | 0,11 | 136,47 | -12 | -12 | 0 | 122 | 36,2 | 105 | MO | AB | ||||||||||||||||
R125 | R404A | >2500 | 0 | CF3CHF2 | HFC | pentafluoro-ethane | 7 | -45 | 0 | 3500 | 3170 | 3740 | A1 | 0,39 | 120,02 | -48,5 | -48,5 | 0 | 66 | 36,3 | 51 | POE | PVE | AB | |||||||||||||||
R134a | R134a | >750..2500 | 0 | CF3CH2F | HFC | 1,1,1,2-tetrafluoro-ethane | R12, R22 | 25 | -20 | -30 | 0 | 1430 | 1300 | 1530 | A1 | 0,25 | 102,03 | -26,1 | -26,1 | 0 | 101 | 40,7 | 79 | 97 (M) | -8 | POE | PVE | AB | |||||||||||
R141b | >150..750 | 0 | CFCl2CH3 | HCFC | 1,1-dichloro-1-fluoro-ethane | 0,11 | 725 | 782 | 860 | 116,95 | 32 | 32 | 0 | 204,35 | 42,12 | 172 | MO | AB | |||||||||||||||||||||
R142b | >750..2500 | 0 | CClF2CH3 | HCFC | 1-chloro-1,1-difluoro-ethane | R114, R12B1 | 20 | -10 | 0,065 | 2310 | 1980 | 2300 | A2 | 0,049 | 100,5 | -9,1 | -9,1 | 0 | 137 | 40,6 | 112 | MO | AB | ||||||||||||||||
R143a | >2500 | 0 | CF3CH3 | HFC | 1,1,1-trifluoro-ethane | 0 | -45 | 0 | 4470 | 4800 | 5810 | A2L | 0,048 | 84,04 | -47,2 | -47,2 | 0 | 73 | 37,6 | 55 | POE | PVE | AB | ||||||||||||||||
R152a | R134a | ≤150 | 0 | CHF2CH3 | HFC | 1,1-difluoro-methane | R12, R22 | 25 | -20 | 0 | 124 | 138 | 164 | A2 | 0,027 | 66,05 | -24 | -24 | 0 | 113 | 45,2 | 85 | POE | PVE | AB | ||||||||||||||
R170 | ≤150 | 0 | CH3CH3 | HC | ethane | R23, R508A, R508B | -50 | -95 | 0 | 6 | 6 | 0,437 | A3 | 0,0086 | 30,07 | -88,6 | -88,6 | 0 | 32 | 48,7 | 4 | PAO | MO | POE | AB | ||||||||||||||
R218 | >2500 | 0 | CF3CF2CF3 | PFC | octafluoro-propane | 0 | 8830 | 8900 | 9290 | A1 | 188,02 | -36,8 | -36,8 | 0 | 71,87 | 26,4 | POE | ||||||||||||||||||||||
R227ea | >2500 | 0 | CF3CHFCF3 | HFC | 1,1,1,2,3,3,3-heptafluoro-propane | R12B1, R114 | 40 | -10 | 0 | 3220 | 3350 | 3600 | A1 | 0,63 | 170,03 | -16,3 | -16,3 | 0 | 102 | 29,3 | 96 | POE | PVE | AB | |||||||||||||||
R236fa | >2500 | 0 | CF3CH2CF3 | HFC | 1,1,1,3,3,3-hexafluoro-propane | R114 | 40 | 0 | 0 | 9810 | 8060 | 8690 | A1 | 0,59 | 152,04 | -1,5 | -1,5 | 0 | 125 | 32 | 115 | POE | PVE | AB | |||||||||||||||
R245fa | >750..2500 | 0 | CF3CH2CF2H | HFC | 1,1,1,3,3-pentafluoro-propane | R123 | 40 | 5 | 0 | 1030 | 856 | 962 | B1 | 0,19 | 134,05 | 15,1 | 15,1 | 0 | 154 | 36,5 | 136 | POE | |||||||||||||||||
R290 | R404A | R22 | ≤150 | 0 | CH3CH2CH3 | HC | propane | R404A, R507A, R22 | 12 | -40 | -20 | -55 | 0 | 3 | 3 | 0,02 | A3 | 0,008 | 44,1 | -42,1 | -42,1 | 0 | 97 | 42,5 | 70 | 86 (M) | 4 | PAO | PAG | POE | AB | MO | |||||||
R600 | ≤150 | 0 | CH3CH2CH2CH3 | HC | butane | 40 | 0 | 0 | 4 | 3 | 0,006 | A3 | 0,011 | 58,12 | -0,5 | -0,5 | 0 | 152 | 38 | 129 | MO | PAO | POE | AB | |||||||||||||||
R600a | R134a | ≤150 | 0 | CH3CHCH3CH3 | HC | isobutane | R134a, R12 | 40 | -10 | -25 | 0 | 3 | 3 | A3 | 0,011 | 58,12 | -11,8 | -11,8 | 0 | 135 | 36,3 | 115 | 55 (H) | -9 | MO | PAO | POE | AB | |||||||||||
R717 | R404A | R22 | ≤150 | 0 | NH3 | NH3 | ammonia | R404A, R507A, R22 | 12 | -20 | -15 | -50 | 0 | 0 | 0 | B2L | 0,00035 | 17,03 | -33,4 | -33,4 | 0 | 132 | 113 | 60 | 100 (M) | 60 | MO | PAO | MO/HC | AB | |||||||||
R718 | ≤150 | 0 | H2O | H2O | water | 60 | 10 | 0 | 0 | 0 | A1 | 18,02 | 100 | 100 | 0 | 373,95 | 220,64 | 226 | 250 | ||||||||||||||||||||
R723 | ≤150 | 0 | NH3/ R-E170 | NH3/ R-E170 | ammonia/ DME | R404A, R507A, R22 | 12 | -20 | -15 | -50 | 0 | 1 | 1 | B2 | 22,77 | -36,5 | -36,5 | 0 | 131 | 110 | 58 | 105 (M) | 35 | MO | PAO | MO/HC | AB | ||||||||||||
R744 | R134a | R404A | R22 | ≤150 | 0 | CO2 | CO2 | carbon dioxide | R23, R134a, R404A, R507A | 20 | -20 | -10 | -50 | 0 | 1 | 1 | 1 | A1 | 0,07 | 44,01 | -78,3 | -78,3 | 0 | 31 | 73,8 | -11 | POE | PAG | |||||||||||
R744A | >150..750 | 0 | N2O | N2O | nitrous oxide | R23, R508A, R508B | -40 | -80 | 0,017 | 298 | 265 | 273 | A1 | 44,01 | -88,5 | -88,5 | 0 | 36 | 72,5 | -7 | special | ||||||||||||||||||
R1130(E) | 0 | CClHCClH | HCO | trans-dichloroethene | Chemours | R123 | 0,0002 | 5 | B2 | 0,004 | 96,94 | 48 | 48 | 0 | 241 | 48,5 | |||||||||||||||||||||||
R1132a | ≤150 | 0 | CF2CH2 | HFO | 1,1-difluoro-ethene | Daikin | R23, R508A, R508B | 0 | 1 | 1 | 0,052 | A2 | 0,033 | 64,03 | -84 | -84 | 0 | 30,1 | 44,33 | POE | |||||||||||||||||||
R1132(E) | ≤150 | 0 | E-CFHCFH | HFO | trans-1,2-difluoro-ethene | Daikin | R404A, R507A | 0 | 1 | B2 | 0,028 | 64,03 | -52,5 | -52,5 | 0 | 75,7 | 51,7 | POE | |||||||||||||||||||||
R1150 | ≤150 | 0 | CH2CH2 | HC | ethylene | R14, R23, R508A, R508B | -50 | -100 | 0 | 4 | 4 | A3 | 0,006 | 28,05 | -103,8 | -103,8 | 0 | 9 | 50,4 | -19 | MO | PAO | |||||||||||||||||
R1224yd(Z) | ≤150 | 0 | (Z)-CF3-CF=CHCl | HCFO | (Z)-1-chloro-2,3,3,3-tetrafluoro-propene | Amolea | R123, R11 | 30 | 0 | 0,00012 | 4 | 1 | A1 | 14,6 | 14,6 | 0 | 156 | 33,3 | 141 | POE | |||||||||||||||||||
R1233zd(E) | ≤150 | 0 | C3H2ClF3 | HCFO | trans-1-chloro-3,3,3-trifluoro-1-propene | R123, R11 | 30 | 0 | 0,00034 | 5 | 1 | 3,88 | A1 | 133,5 | 18,3 | 18,3 | 0 | 166 | 36,2 | 147 | POE | ||||||||||||||||||
R1234yf | R134a | ≤150 | 0 | CF3FCH2 | HFO | 2,3,3,3-tetrafluoro-1-propene | Chemours, Honeywell | R134a | 25 | -25 | -30 | 0 | 4 | 1 | 0,501 | A2L | 0,058 | 114,04 | -29,5 | -29,5 | 0 | 95 | 33,8 | 82 | 98 (M) | -14 | POE | PVE | |||||||||||
R1234ze(E) | R134a | ≤150 | 0 | C3H2F4 | HFO | trans-1,3,3,3-tetrafluoro-1-propene | Honeywell | R134a | 40 | -10 | 0 | 6 | 1 | 1,37 | A2L | 0,061 | 114,04 | -19 | -19 | 0 | 109 | 36,4 | 92 | 75 (H) | -6 | POE | PVE | ||||||||||||
R1270 | R404A | R22 | ≤150 | 0 | CH2CHCH3 | HC | propylene / propene | R404A, R507A, R22 | 12 | -40 | -20 | -55 | 0 | 2 | 2 | A3 | 0,008 | 42,08 | -47,6 | -47,6 | 0 | 91 | 45,6 | 61 | 104 (M) | 12 | PAO | PAG | POE | AB | MO | ||||||||
R1336mzz(E) | ≤150 | 0 | C4H2F6 | HFO | trans-1,1,1,4,4,4-hexafluoro-2-butene | R245fa | 40 | 0 | 0 | 18 | 7 | 17,9 | A1 | 0,048 | 164,06 | 7,6 | 7,6 | 0 | 130 | 27,66 | 126 | POE | special | ||||||||||||||||
R1336mzz(Z) | ≤150 | 0 | C4H2F6 | HFO | cis-1,1,1,4,4,4-hexafluoro-2-butene | R123, R245fa | 40 | 0 | 0 | 9 | 2 | 2,08 | A1 | 0,087 | 164,06 | 33,5 | 33,5 | 0 | 171 | 29 | 165 | POE | special | ||||||||||||||||
MO89 | >2500 | >0..4 | HFC | R125/ 218/ 290 | ISCEON MO89 | R13B1 | -20 | -45 | -40 | -80 | 0 | 3805 | 3324 | A1 | 113,92 | -53,2 | -50,3 | 2,9 | 62 | 35,6 | 48 | POE | PVE | AB | |||||||||||||||
R401A | >750..2500 | >4..8 | HCFC | R22/ 152a/ 124 | 0,04 | 1182 | 1130 | A1 | 94,44 | -32,9 | -27,2 | 5,7 | 107,75 | 46,41 | 80 | 101 | MO | AB | |||||||||||||||||||||
R401B | >750..2500 | >4..8 | HCFC | R22/ 152a/ 124 | 0,04 | 1288 | 1240 | A1 | 92,84 | -34,6 | -29 | 5,6 | 106,03 | 47,25 | 77 | 98 | MO | AB | |||||||||||||||||||||
R402A | >2500 | >0..4 | HCFC | R125/ 290/ 22 | 0,02 | 2788 | 2570 | A1 | 101,55 | -48,9 | -47 | 1,9 | 75,07 | 41,54 | 53 | AB | POE | ||||||||||||||||||||||
R402B | >750..2500 | >0..4 | HCFC | R125/ 290/ 22 | 0,03 | 2416 | 2260 | A1 | 94,71 | -47 | -44,8 | 2,2 | 82,38 | 44,69 | 57 | 77 | AB | POE | |||||||||||||||||||||
R403A | >2500 | >0..4 | HCFC | R290/ 22/ 218 | 0,04 | 3124 | 3100 | A1 | 91,98 | -47,4 | -44,3 | 3,1 | 84,42 | 44,55 | 58 | 79 | AB | POE | |||||||||||||||||||||
R403B | >2500 | >0..4 | HCFC | R290/ 22/ 218 | 0,03 | 4457 | 4460 | A1 | 103,26 | -48,6 | -46,8 | 1,8 | 76,27 | 39,98 | 56 | AB | POE | ||||||||||||||||||||||
R404A | R404A | >2500 | >0..4 | HFC | R143a/ 125/ 134a | R502, R22 | 0 | -45 | 7 | -30 | -70 | 0 | 3922 | 3940 | 4728 | A1 | 0,52 | 97,6 | -46,2 | -45,5 | 0,7 | 72 | 37,35 | 56 | 105 (M) | -34 | POE | PVE | AB | ||||||||||
R407A | R404A | R22 | >750..2500 | >4..8 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 0 | -40 | 7 | -30 | -55 | 0 | 2107 | 1920 | 2262 | A1 | 0,33 | 90,11 | -45,2 | -38,7 | 6,5 | 82 | 44,94 | 59 | 98 (M) | -19 | POE | PVE | AB | |||||||||
R407B | >2500 | >4..8 | HFC | R32/ 125/ 134a | 0 | 2804 | 2550 | 3001 | A1 | 102,94 | -46,5 | -42,3 | 4,2 | 74,75 | 41,11 | 55 | POE | ||||||||||||||||||||||
R407C | R22 | >750..2500 | >4..8 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 12 | -25 | -30 | 0 | 1774 | 1620 | 1908 | A1 | 0,31 | 86,2 | -43,8 | -36,7 | 7,1 | 86 | 46,15 | 61 | 100 (H) | -8 | POE | PVE | AB | ||||||||||||
R407F | R404A | R22 | >750..2500 | >4..8 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 0 | -40 | 7 | -30 | -55 | 0 | 1825 | 1674 | 1965 | A1 | 0,32 | 82,06 | -46,1 | -39,7 | 6,4 | 83 | 47,55 | 57 | 104 (M) | -11 | POE | PVE | AB | |||||||||
R407H | R404A | R22 | >750..2500 | >4..8 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 0 | -30 | 7 | -35 | 0 | 1490 | 1380 | 1615 | A1 | 0,38 | 79,1 | -44,6 | -37,6 | 7 | 87 | 48,57 | 60 | 99 (M) | -8 | POE | PVE | AB | ||||||||||
R408A | >2500 | >0..4 | HCFC | R125/ 143a/ 22 | 0,03 | 3152 | 3260 | A1 | 87,01 | -44,6 | -44,1 | 0,5 | 83,05 | 42,86 | 59 | AB | POE | ||||||||||||||||||||||
R409A | >750..2500 | >8 | HCFC | R22/ 124/ 142b | 0,05 | 1585 | 1480 | A1 | 97,43 | -34,5 | -26 | 8,5 | 110,3 | 47,62 | 81 | 102 | MO | AB | |||||||||||||||||||||
R409B | >750..2500 | >4..8 | HCFC | R22/ 124/ 142b | 0,05 | 1560 | 1470 | A1 | 96,67 | -35,6 | -27,9 | 7,7 | 107,58 | 47,91 | 78 | 99 | MO | AB | |||||||||||||||||||||
R410A | R22 | R410A | >750..2500 | 0 | HFC | R32/ 125 | R22, R13B1 | 12 | -25 | -40 | -40 | -80 | 0 | 2088 | 1920 | 2256 | A1 | 0,44 | 72,59 | -51,4 | -51,4 | 0 | 71 | 49,01 | 43 | 140 (H) | -4 | POE | PVE | AB | |||||||||
R411A | >750..2500 | >0..4 | HCFC | R1270/ 22/ 152a | 0,05 | 1597 | 1560 | A2 | 82,36 | -39,5 | -36,6 | 2,9 | 99,23 | 49,63 | 67 | 88 | MO | AB | |||||||||||||||||||||
R411B | >750..2500 | >0..4 | HCFC | R1270/ 22/ 152a | 0,05 | 1705 | 1660 | A2 | 83,07 | -41,6 | -40 | 1,6 | 96,04 | 49,55 | 64 | 85 | MO | AB | |||||||||||||||||||||
R413A | >750..2500 | >4..8 | HFC | R218/ 134a/ 600a | 0 | 2053 | 1950 | A1 | 103,95 | -33,4 | -28,1 | 5,3 | 95,33 | 39,2 | 76 | AB | POE | ||||||||||||||||||||||
R417A | R134a | R22 | >750..2500 | >4..8 | HFC | R125/ 134a/ 600 | R22 | 12 | -25 | -30 | 0 | 2346 | 2130 | A1 | 0,15 | 106,75 | -39,1 | -34,1 | 5 | 85 | 38,94 | 67 | 97 (M) | -25 | POE | PVE | AB | ||||||||||||
R417B | R134a | R22 | >2500 | >0..4 | HFC | R125/ 134a/ 600 | R22 | 0 | -40 | 7 | 0 | 2920 | 2740 | A1 | 0,069 | 113,12 | -44,9 | -41,5 | 3,4 | 74 | 37,37 | 58 | 95 (M) | -37 | POE | PVE | AB | ||||||||||||
R418A | >750..2500 | >0..4 | HCFC | R290/ 22/ 152a | 0,033 | 1741 | 1690 | A2 | 84,59 | -41,7 | -40 | 1,7 | 95,98 | 49,61 | 64 | 85 | MO | AB | |||||||||||||||||||||
R419A | >2500 | >4..8 | HFC | R125/ 134a/ E170 | 0 | 2967 | 2690 | A2 | 109,34 | -42,6 | -35,9 | 6,7 | 83,5 | 40,6 | 56 | POE | |||||||||||||||||||||||
R420A | >750..2500 | >0..4 | HCFC | R134a/ 142b | 0,005 | 1536 | 1380 | A1 | 101,85 | -25 | -24,2 | 0,8 | 104,76 | 40,86 | 83 | POE | |||||||||||||||||||||||
R421A | >2500 | >4..8 | HFC | R125/ 134a | 0 | 2631 | 2380 | A1 | 111,75 | -40,7 | -35,4 | 5,3 | 82,77 | 39,18 | 65 | POE | |||||||||||||||||||||||
R421B | >2500 | >0..4 | HFC | R125/ 134a | 0 | 3190 | 2890 | A1 | 116,93 | -45,6 | -42,4 | 3,2 | 72,38 | 37,46 | 56 | POE | |||||||||||||||||||||||
R422A | R22 | >2500 | >0..4 | HFC | R125/ 134a/ 600a | R22 | 0 | -40 | 7 | 0 | 3143 | 2850 | A1 | 0,29 | 113,6 | -46,5 | -44 | 2,5 | 71 | 36,65 | 55 | 100 (M) | -39 | POE | PVE | AB | |||||||||||||
R422B | >2500 | >4..8 | HFC | R125/ 134a/ 600a | 0 | 2526 | 2290 | A1 | 108,52 | -41,3 | -35,9 | 5,4 | 81,98 | 38,57 | 65 | POE | |||||||||||||||||||||||
R422C | >2500 | >0..4 | HFC | R125/ 134a/ 600a | 0 | 3085 | 2790 | A1 | 113,4 | -45,9 | -42,9 | 3 | 72,07 | 36,96 | 57 | POE | |||||||||||||||||||||||
R422D | R22 | >2500 | >4..8 | HFC | R125/ 134a/ 600a | R22 | 0 | -40 | 7 | 0 | 2729 | 2470 | A1 | 0,26 | 109,94 | -43,2 | -38,3 | 4,9 | 78 | 37,95 | 62 | 90 (M) | -36 | POE | PVE | AB | |||||||||||||
R427A | R22 | >750..2500 | >4..8 | HFC | R32/ 125/ 143a/ 134a | R22 | 0 | -40 | 7 | 0 | 2138 | 2020 | A1 | 0,29 | 90,44 | -43 | -36,2 | 6,8 | 85 | 44,06 | 63 | 90 (M) | -20 | POE | PVE | AB | |||||||||||||
R434A | >2500 | >0..4 | HFC | R125/ 143a/ 134a/ 600a | 0 | 3245 | 3080 | A1 | 105,74 | -45 | -42,3 | 2,7 | 74,14 | 37,32 | 58 | POE | |||||||||||||||||||||||
R437A | >750..2500 | >0..4 | HFC | R125/ 134a/ 600/ 601 | R12 | 12 | -30 | 0 | 1805 | 1640 | A1 | 0,081 | 103,71 | -32,4 | -28,9 | 3,5 | 95 | 40,03 | 75 | 108 (M) | -7 | POE | PVE | AB | |||||||||||||||
R438A | R134a | R22 | >750..2500 | >4..8 | HFC | R32/ 125/ 134a/ 600/ 601a | R22 | 0 | -40 | 7 | 0 | 2264 | 2060 | A1 | 0,079 | 99,13 | -42,3 | -35,7 | 6,6 | 83 | 41,79 | 63 | 88 (M) | -27 | POE | PVE | AB | ||||||||||||
R442A | >750..2500 | >4..8 | HFC | R32/ 125/ 134a/ 152a/ 227ea | R404A, R507A | 0 | -40 | 0 | 1888 | 1750 | A1 | 0,33 | 81,76 | -46,4 | -39,7 | 6,7 | 82 | 47,48 | 57 | POE | PVE | ||||||||||||||||||
R443A | R404A | R22 | ≤150 | >0..4 | HC | R1270/ 290/ 600a | 0 | 4 | 4 | A3 | 43,47 | -45,2 | -42,1 | 3,1 | 96,01 | 44,85 | 68 | 90 | PAO | POE | MO | PAG | |||||||||||||||||
R444A | R134a | ≤150 | >8 | HFO/ HFC | R32/ 152a/ 1234ze(E) | AC5 | Koura (Mexichem) | R134a | 25 | -20 | 0 | 92 | 89 | A2L | 0,29 | 96,7 | -35,7 | -24,6 | 11,1 | 106 | 44,73 | 81 | POE | PVE | |||||||||||||||
R444B | R22 | >150..750 | >8 | HFO/HFC | R32/ 152a/ 1234ze(E) | L-20 | Honeywell | R407C, R22 | 12 | -35 | 0 | 295 | 295 | A2L | 0,055 | 72,76 | -45 | -35 | 10 | 92 | 52,1 | POE | PVE | ||||||||||||||||
R447B | R410A | >150..750 | >0..4 | HFO/HFC | R32/ 125/ 1234ze(E) | L-41z | Honeywell | R410A | 15 | -25 | 0 | 740 | 714 | A2L | -50 | -46 | 4 | 84 | 49 | 68 | POE | PVE | |||||||||||||||||
R448A | R404A | >750..2500 | >4..8 | HFO/ HFC | R32/ 125/ 1234yf/ 1234ze(E)/ 134a | N-40 | Honeywell | R404A, R507A | 12 | -40 | -45 | -25 | -65 | 0 | 1387 | 1273 | 1494 | A1 | 0,388 | 86,28 | -46,1 | -39,9 | 6,2 | 83 | 45,95 | 58 | 96 (M) | 12 | POE | PVE | |||||||||
R449A | R404A | >750..2500 | >4..8 | HFO/ HFC | R32/ 125/ 1234yf/ 134a | XP40, 449A | Chemours, Arkema | R404A, R507A | 12 | -40 | -45 | -25 | -65 | 0 | 1397 | 1282 | 1504 | A1 | 0,357 | 87,21 | -45,7 | -40 | 5,7 | 82 | 45 | 58 | 77 | 96 (M) | 12 | POE | PVE | ||||||||
R449B | R404A | >750..2500 | >4..8 | HFO/HFC | R32/ 125/ 1234yf/ 134a | Arkema | R404A, R507A | 12 | -40 | -25 | -65 | 0 | 1412 | 1296 | A1 | -46 | -40 | 6 | 84 | 44,3 | POE | PVE | |||||||||||||||||
R449C | R22 | >750..2500 | >4..8 | HFO/ HFC | R32/ 125/ 1234yf/ 134a | Chemours | R407C, R22 | 12 | -35 | 0 | 1251 | 1146 | A1 | 0,362 | -44 | -38 | 6 | 84 | 61 | 81 | POE | PVE | |||||||||||||||||
R450A | R134a | >150..750 | >0..4 | HFO/ HFC | R1234ze(E)/ 134a | N-13 | Honeywell | R134a, R12 | 25 | -25 | 0 | 604 | 547 | 643 | A1 | 0,319 | 108,67 | -23,4 | -22,8 | 0,6 | 104 | 38,2 | 86 | 88 (M) | -6 | POE | PVE | ||||||||||||
R452A | R404A | >750..2500 | >0..4 | HFO/ HFC | R32/ 125/ 1234yf | XP44 | Chemours | R404A, R507A | 12 | -40 | -25 | -65 | 0 | 2140 | 1945 | 2292 | A1 | 0,423 | 103,51 | -46,9 | -43,1 | 3,8 | 75 | 40,03 | 56 | 75 | POE | PVE | |||||||||||
R452B | R404A | R410A | >150..750 | >0..4 | HFO/ HFC | R32/ 125/ 1234yf | XL55, L-41y | Chemours, Honeywell | R410A | 15 | -25 | 0 | 698 | 676 | 779 | A2L | 0,062 | 63,53 | -50,7 | -49,8 | 0,9 | 77 | 52,2 | 46 | 65 | 98 (H) | 7 | POE | PVE | ||||||||||
R452C | R404A | >750..2500 | >0..4 | HFO/HFC | R32/ 125/ 1234yf | Arkema | R404A, R507A | 12 | -40 | -25 | -65 | 0 | 2220 | 2019 | A1 | 0,43 | 101,95 | -47,5 | -44,1 | 3,4 | 74 | 40,55 | 52 | 73 | POE | PVE | |||||||||||||
R454A | R404A | >150..750 | >4..8 | HFO/ HFC | R32/ 1234yf | XL40, ARM-20b | Chemours, Arkema | R404A, R507A | 12 | -40 | -25 | -65 | 0 | 239 | 238 | 270 | A2L | 0,056 | 79,79 | -47,9 | -42,2 | 5,7 | 82 | 46,3 | 57 | 76 | POE | PVE | |||||||||||
R454B | R410A | >150..750 | >0..4 | HFO/ HFC | R32/ 1234yf | XL41 | Chemours | R410A | 15 | -25 | 0 | 466 | 467 | 531 | A2L | 0,061 | 62,61 | -50,5 | -49,5 | 1 | 78 | 52,67 | 47 | 66 | 97 (H) | 0 | POE | PVE | |||||||||||
R454C | R404A | ≤150 | >4..8 | HFO/ HFC | R32/ 1234yf | XL20 | Chemours | R404A, R507A | 12 | -40 | -25 | -65 | 0 | 148 | 146 | 166 | A2L | 0,059 | 90,78 | -45,6 | -37,8 | 7,8 | 86 | 43,2 | 64 | 83 | POE | PVE | |||||||||||
R455A | R404A | ≤150 | >8 | HFO/ HFC | R32/ 1234yf/ 744 | L-40X | Honeywell | R404A, R507A | 12 | -40 | -25 | -65 | 0 | 148 | 146 | 166 | A2L | 0,105 | 87,45 | -52 | -39,2 | 12,8 | 86 | 46,5 | 61 | 93 (M) | 10 | POE | PVE | ||||||||||
R456A | R134a | >150..750 | >4..8 | HFO/ HFC | R32/ 1234ze(E)/ 134a | AC5X | Koura (Mexichem) | R134a | 25 | -25 | 0 | 687 | 627 | A1 | 0,32 | 101,42 | -30,8 | -25,4 | 5,4 | 103 | 41,75 | 80 | POE | PVE | |||||||||||||||
R457A | R404A | ≤150 | >4..8 | HFO/ HFC | R32/ 1234yf/ 152a | ARM-20a | Arkema | R404A, R507A | 12 | -40 | -25 | -65 | 0 | 139 | 139 | A2L | 0,043 | 87,61 | -42,6 | -35,5 | 7,1 | 90 | 43,08 | 68 | 85 | POE | PVE | ||||||||||||
R457B | R404A | >150..750 | >4..8 | HFO/HFC | R32/ 1234yf/ 152a | ARM-20b | Arkema | R404A, R507A | 7 | -45 | 0 | 276 | 279 | 319 | A2L | 76,5 | -46,4 | -40,4 | 6 | POE | PVE | ||||||||||||||||||
R457C | R404A | ≤150 | >4..8 | HFO/HFC | R32/ 1234yf/ 152a | Chemours | R134a | 12 | -35 | 0 | 72 | 72 | 82 | A2L | 0,054 | 95,4 | -37,3 | -32,1 | 5,2 | 94,1 | 39,6 | POE | PVE | ||||||||||||||||
R459A | R410A | >150..750 | >0..4 | HFO/HFC | R32/ 1234yf/ 1234ze(E) | ARM-71a | Arkema | R410A | 15 | -25 | 0 | 460 | 461 | A2L | 0,056 | 62,98 | -50,3 | -48,5 | 1,8 | 80 | 53,4 | 46 | 65 | POE | PVE | ||||||||||||||
R459B | R404A | ≤150 | >8 | HFO/HFC | R32/ 1234yf/ 1234ze(E) | LTR11 | Mexichem | R404A, R507A | 7 | -35 | 0 | 144 | 143 | A2L | 0,48 | 91,21 | -45 | -36,7 | 8,3 | 87 | 43,61 | 66 | POE | PVE | |||||||||||||||
R460A | R404A | >750..2500 | >4..8 | HFO/HFC | R32/ 1234ze(E)/ R134a | LTR10 | Mexichem | R404A, R507A | 7 | -35 | 0 | 2103 | 1911 | A1 | 0,38 | 100,6 | -44,6 | -36,6 | 8 | 84 | 43,36 | 61 | POE | PVE | |||||||||||||||
R460B | R404A | >750..2500 | >8 | HFO/HFC | R32/ 1234ze(E)/ R134a | LTR4X | Mexichem | R404A, R507A | 7 | -35 | 0 | 1352 | 1242 | A1 | 0,399 | 84,8 | -45,6 | -36,9 | 8,7 | 88 | 48,9 | 60 | POE | PVE | |||||||||||||||
R463A | >750..2500 | >8 | HFO/ HFC | R32/ 125/ 1234yf/ 134a/ 744 | XP41 | Chemours | R410A | 15 | -25 | 0 | 1494 | 1377 | A1 | 0,299 | 74,72 | -59,9 | -46,9 | 13 | 76 | 52,44 | 47 | 65 | POE | PVE | |||||||||||||||
R465A | R404A | ≤150 | >8 | HFO/ HFC | R32/ 1234yf/ 290 | ARM-25 | Arkema | R404A, R507A | 7 | -40 | 0 | 145 | 143 | 162 | A2 | 0,04 | 82,9 | -51,7 | -40 | 11,7 | 82 | 43,36 | 60 | POE | PVE | ||||||||||||||
R466A | R410A | >150..750 | >0..4 | HFO/ HFC | R32/ 1234yf/ 13I1 | N-41 | Honeywell | R410A | 15 | -25 | 0 | 733 | 696 | A1 | 0,099 | 80,69 | -51,7 | -51 | 0,7 | 76 | 51,44 | 46 | 65 | POE | PVE | ||||||||||||||
R468A | R404A | ≤150 | >8 | HFO/ HFC | R32/ 1234yf/ 1132a | Daikin Chemical | R404A, R507A, R22 | 0 | -40 | 0 | 148 | 147 | 166 | A2L | 88,8 | -51,2 | -39 | 12,2 | 84 | 44,54 | 62 | POE | |||||||||||||||||
R468B | R410A | ≤150 | >8 | HFO/HFC | R32/ 1234yf/ 1132a | Koura/Mexichem | R410A, R404A, R507A | 0 | -40 | 0 | 101 | A2L | 0,07 | 94,9 | -52,4 | -36,8 | 15,6 | 85 | 42,5 | POE | |||||||||||||||||||
R468C | R410A | >150..750 | >8 | HFO/HFC | R32/ 1234yf/ 1132a | Koura/Mexichem | R410A | 15 | -25 | 0 | 324 | A2L | 0,069 | 73,7 | -56,6 | -46,2 | 10,4 | 76,8 | 48,9 | POE | |||||||||||||||||||
R469A | >750..2500 | >8 | HFC/ CO2 | R744/ 32/ 125 | WT69 | TEGA | R23 | -40 | -75 | 0 | 1358 | 1250 | 1621 | A1 | 59,1 | -78,5 | -61,5 | 17 | 59 | 65,17 | 23 | POE | |||||||||||||||||
R471A | R134a | ≤150 | >0..4 | HFO/ HFC | R1234ze(E)/ 1336mzz(E)/ 227ea | Honeywell | (R134a) | 20 | -20 | 0 | 148 | 148 | 148 | A1 | 122,09 | -16,9 | -13,7 | 3,2 | 112 | 35,34 | 97 | 67 (H) | -7 | POE | |||||||||||||||
R472A | >150..750 | >8 | HFC/CO2 | R744/ 32/ 134a | Angeletoni | R23 | 0 | 353 | 329 | 384 | A1 | 0,072 | 50,39 | -84,3 | -61,5 | 22,8 | 50,2 | 77,5 | POE | ||||||||||||||||||||
R472B | >150..750 | >8 | HFC/CO2 | R744/ 32/ 134a | Angeletoni | R23 | 0 | 526 | 484 | 567 | A1 | 0,08 | 54,8 | -82,9 | -54,8 | 28,1 | 57,9 | 77,1 | POE | ||||||||||||||||||||
R473A | >750..2500 | >0..4 | HFO/HFC | R744/ 1132a/ 23/ 125 | Koura/Mexichem | R23 | 0 | 1830 | 1558 | 1835 | A1 | 0,077 | 52,58 | -75,8 | -72,1 | 3,7 | 29,72 | 62,87 | -5 | 11 | POE | ||||||||||||||||||
R474A | R134a | ≤150 | >4..8 | HFO | R1132(E)/ 1234yf | Daikin | R134a | 10 | -35 | 0 | 2 | A2L | 0,053 | 96,7 | -43,1 | -36,4 | 6,7 | 87,1 | 40,4 | POE | |||||||||||||||||||
R475A | R134a | >150..750 | >0..4 | HFO/HFC | R134a/ 1234yf/ 1234ze(E) | Gree | R134a | 15 | -30 | 0 | 619 | 560 | 659 | A1 | 0,32 | 108,54 | -28,8 | -28,3 | 0,5 | 99,3 | 37,2 | POE | |||||||||||||||||
R476A | R134a | ≤150 | >0..4 | HFO/HFC | R134a/ 1234ze(E)/ 1336mzz(E) | Honeywell | R134a | 25 | -15 | 0 | 132 | 156 | A1 | 0,18 | 116,9 | -19,1 | -16,1 | 3 | 110 | 36,3 | POE | ||||||||||||||||||
R500 | >2500 | 0 | CFC | R12/ 152a | 10 | -30 | 0,74 | 8077 | 7560 | A1 | 0,4 | 99,3 | -33,6 | -33,6 | 0 | 102 | 41,68 | 78 | MO | AB | |||||||||||||||||||
R502 | R404A | >2500 | 0 | CFC | R22/ 115 | 10 | -50 | 0,33 | 4657 | 4790 | A1 | 0,45 | 111,64 | -45,4 | -45,4 | 0 | 82 | 40,7 | 60 | AB | |||||||||||||||||||
R503 | >2500 | 0 | CFC | R13/ 23 | -50 | -90 | 0,6 | 14560 | 13300 | A1 | 0,35 | 87,24 | -87,9 | -87,9 | 0 | 20 | 43,43 | -2 | AB | ||||||||||||||||||||
R507A | R404A | >2500 | 0 | HFC | R143a/ 125 | R502, R22 | 0 | -45 | 7 | -30 | -70 | 0 | 3985 | 3990 | 4775 | A1 | 0,53 | 98,86 | -46,7 | -46,7 | 0 | 71 | 37,05 | 54 | 107 (M) | -34 | POE | PVE | AB | ||||||||||
R508A | >2500 | 0 | HFC | R23/ 116 | R503 | -50 | -95 | 0 | 13210 | 11600 | A1 | 0,23 | 100,1 | -87,6 | -87,6 | 0 | 10 | 36,48 | -3 | POE | |||||||||||||||||||
R508B | >2500 | 0 | HFC | R23/ 116 | R503 | -50 | -95 | 0 | 13400 | 11700 | A1 | 0,25 | 95,39 | -87,6 | -87,6 | 0 | 11 | 37,71 | -3 | POE | |||||||||||||||||||
R511A | ≤150 | 0 | HC | R290/ E170 | 0 | 3 | 3 | A3 | 44,19 | -42 | -42 | 0 | 96,98 | 42,88 | 70 | PAO | POE | MO | |||||||||||||||||||||
R513A | R134a | >150..750 | >0..4 | HFO/ HFC | R1234yf/ 134a | XP10 | Chemours | R134a, R12, R404A | 25 | -25 | -30 | 0 | 631 | 573 | 673 | A1 | 0,319 | 108,31 | -29,6 | -29,5 | 0,1 | 95 | 36,5 | 78 | 102 (M) | -7 | POE | PVE | |||||||||||
R513B | R134a | >150..750 | 0 | HFO/HFC | R1234yf/ 134a | Daikin Chemical | R134a | 25 | -25 | 0 | 596 | 540 | 895 | A1 | 108,73 | -29,6 | -29,6 | 0 | 95 | 36,32 | 79 | POE | PVE | ||||||||||||||||
R514A | ≤150 | 0 | HFO | R1336mzz(Z)/ 1130(E) | XP30 | Chemours | R11, R123, (R134a) | 40 | 0 | 0 | 7 | 2 | B1 | 0,013 | 139,6 | 28,8 | 28,8 | 0 | 178 | 34,7 | 161 | POE | |||||||||||||||||
R515B | R134a | >150..750 | 0 | HFO/ HFC | R1234ze(E)/ 227ea | N-15 | Honeywell | R134a | 20 | -20 | 0 | 293 | 299 | 322 | A1 | 0,29 | 117,48 | -18,8 | -18,8 | 0 | 109 | 35,84 | 93 | 75 (H) | -7 | POE | |||||||||||||
R516A | R134a | ≤150 | 0 | HFO/ HFC | R1234yf/ 152a/ 134a | ARM-42 | Arkema | R134a | 25 | -25 | 0 | 142 | 131 | 153 | A2L | 0,042 | 102,58 | -29,4 | -29,4 | 0 | 97 | 36,23 | 80 | POE |