Complete table with filter function

In the following table refrigerants can be selected and compared with the help of filters. To ease the typical search, some extra columns are introduced for filtering:

Data for the most of the listed refrigerants can also be found in the BITZER RefRuler App.

Refrigerant

R134a similar

R404A similar

R22 similar

R410A similar

GWP range

Temp. glide range

Chemical

Group

Components

Name

Manufacturer

Substitute for

Application max (°C)

Application min (°C)

Appl. limitations max (°C)

Appl. limitations min (°C)

Appl. 2-stage max (°C)

Appl. 2-stage min (°C)

ODP

GWP AR4

GWP AR5

GWP AR6

Safety class

Pract. limit AEL (kg/m³)

Molar mass

Normal boiling point (°C)

Normal dew point (°C)

Temperature glide (K)

Crit. temp. (°C)

Crit. pressure (bar)

Cond. temp. at 26 bar abs (°C)

Cond. temp. at 40 bar abs (°C)

Relative refr. capacity (%)

Discharge temp. increase (K)

Oil 1

Oil 2

Oil 3

Oil with limitations 1

Oil with limitations 2

R11

>2500

0

CCl3F

CFC

trichloro-fluoro-methane

30

0

1

4750

4660

5560

A1

0,3

137,37

23,8

23,8

0

198

44,1

163

MO

AB

R12

R134a

>2500

0

CCl2F2

CFC

dichloro-difluoro-methane

20

-30

1

10900

10200

11200

A1

0,5

120,91

-29,8

-29,8

0

112

41,2

86

MO

AB

R13

>2500

0

CClF3

CFC

chloro-trifluoro-methane

-30

-80

1

14400

13900

16200

A1

0,5

104,46

-81,4

-81,4

0

29

38,7

11

MO

AB

R13B1

>2500

0

CBrF3

Halon

trifluoro-bromo-methane

-10

-60

10

7140

6290

7200

A1

0,6

148,92

-57,7

-57,7

0

67

39,9

46

MO

AB

R13I1

≤150

0

CF3I

IFC

trifluoro-iodo-methane

0,01

1

1

A1

195,91

-21,9

-21,9

0

123

39,5

99

POE

R14

>2500

0

CF4

PFC

tetrafluoro-methane

-90

-125

0

7390

6630

7380

A1

0,4

88,01

-127,9

-127,9

0

-46

37,5

-58

POE

R22

R22

>750..2500

0

CHClF2

HCFC

chloro-difluoro-methane

R502, R12

12

-45

-20

-50

0,055

1810

1760

1960

A1

0,3

86,47

-40,7

-40,7

0

96

49,9

63

80 (L)

35

MO

AB

R23

>2500

0

CHF3

HFC

trifluoro-methane

R13, R503

-50

-95

0

14800

12400

14600

A1

0,68

70,01

-82

-82

0

26

48,3

2

POE

PVE

AB

R32

R410A

>150..750

0

CH2F2

HFC

difluoro-methane

R410A

15

-15

0

675

677

771

A2L

0,061

52,02

-51,7

-51,7

0

78

57,8

42

61

108 (H)

21

POE

PVE

AB

R40

≤150

0

CClH3

ClC

methyl chloride

20

-20

0,02

13

12

5,54

B2

50,48

-23,8

-23,8

0

143

66,8

MO

R113

>2500

0

CFCl2CF2Cl

CFC

trichloro-trifluoro-ethane

0,8

6130

5820

6520

A1

187,38

47,6

47,6

0

214,05

34,15

196

MO

AB

R114

>2500

0

CF2ClCF2Cl

CFC

dichloro-tetrafluoro-ethane

1

10000

8590

9430

A1

170,93

3,6

3,6

0

145,7

32,63

132

MO

AB

R115

>2500

0

CF3CF2Cl

CFC

chloro-pentafluoro-ethane

0,44

7370

7670

9600

A1

154,47

-39,2

-39,2

0

79,95

31,29

71

MO

AB

R116

>2500

0

CF3CF3

PFC

hexafluoro-ethane

0

12200

11100

12400

A1

138,01

-78,1

-78,1

0

19,88

30,48

14

POE

AB

R123

≤150

0

CClF2CClFH

HCFC

dichloro-trifluoro-ethane

R11

20

0

0,02

77

79

90,4

B1

0,1

152,92

27,8

27,8

0

184

36,6

163

MO

AB

R124

>150..750

0

CHClFCF3

HCFC

chloro-tetrafluoro-ethane

R114, R12B1

40

5

0,022

609

527

597

A1

0,11

136,47

-12

-12

0

122

36,2

105

MO

AB

R125

R404A

>2500

0

CF3CHF2

HFC

pentafluoro-ethane

7

-45

0

3500

3170

3740

A1

0,39

120,02

-48,5

-48,5

0

66

36,3

51

POE

PVE

AB

R134a

R134a

>750..2500

0

CF3CH2F

HFC

1,1,1,2-tetrafluoro-ethane

R12, R22

25

-20

-30

0

1430

1300

1530

A1

0,25

102,03

-26,1

-26,1

0

101

40,7

79

97 (M)

-8

POE

PVE

AB

R141b

>150..750

0

CFCl2CH3

HCFC

1,1-dichloro-1-fluoro-ethane

0,11

725

782

860

116,95

32

32

0

204,35

42,12

172

MO

AB

R142b

>750..2500

0

CClF2CH3

HCFC

1-chloro-1,1-difluoro-ethane

R114, R12B1

20

-10

0,065

2310

1980

2300

A2

0,049

100,5

-9,1

-9,1

0

137

40,6

112

MO

AB

R143a

>2500

0

CF3CH3

HFC

1,1,1-trifluoro-ethane

0

-45

0

4470

4800

5810

A2L

0,048

84,04

-47,2

-47,2

0

73

37,6

55

POE

PVE

AB

R152a

R134a

≤150

0

CHF2CH3

HFC

1,1-difluoro-methane

R12, R22

25

-20

0

124

138

164

A2

0,027

66,05

-24

-24

0

113

45,2

85

POE

PVE

AB

R170

≤150

0

CH3CH3

HC

ethane

R23, R508A, R508B

-50

-95

0

6

6

0,437

A3

0,0086

30,07

-88,6

-88,6

0

32

48,7

4

PAO

MO

POE

AB

R218

>2500

0

CF3CF2CF3

PFC

octafluoro-propane

0

8830

8900

9290

A1

188,02

-36,8

-36,8

0

71,87

26,4

POE

R227ea

>2500

0

CF3CHFCF3

HFC

1,1,1,2,3,3,3-heptafluoro-propane

R12B1, R114

40

-10

0

3220

3350

3600

A1

0,63

170,03

-16,3

-16,3

0

102

29,3

96

POE

PVE

AB

R236fa

>2500

0

CF3CH2CF3

HFC

1,1,1,3,3,3-hexafluoro-propane

R114

40

0

0

9810

8060

8690

A1

0,59

152,04

-1,5

-1,5

0

125

32

115

POE

PVE

AB

R245fa

>750..2500

0

CF3CH2CF2H

HFC

1,1,1,3,3-pentafluoro-propane

R123

40

5

0

1030

856

962

B1

0,19

134,05

15,1

15,1

0

154

36,5

136

POE

R290

R404A

R22

≤150

0

CH3CH2CH3

HC

propane

R404A, R507A, R22

12

-40

-20

-55

0

3

3

0,02

A3

0,008

44,1

-42,1

-42,1

0

97

42,5

70

86 (M)

4

PAO

PAG

POE

AB

MO

R600

≤150

0

CH3CH2CH2CH3

HC

butane

40

0

0

4

3

0,006

A3

0,011

58,12

-0,5

-0,5

0

152

38

129

MO

PAO

POE

AB

R600a

R134a

≤150

0

CH3CHCH3CH3

HC

isobutane

R134a, R12

40

-10

-25

0

3

3

A3

0,011

58,12

-11,8

-11,8

0

135

36,3

115

55 (H)

-9

MO

PAO

POE

AB

R717

R404A

R22

≤150

0

NH3

NH3

ammonia

R404A, R507A, R22

12

-20

-15

-50

0

0

0

B2L

0,00035

17,03

-33,4

-33,4

0

132

113

60

100 (M)

60

MO

PAO

MO/HC

AB

R718

≤150

0

H2O

H2O

water

60

10

0

0

0

A1

18,02

100

100

0

373,95

220,64

226

250

R723

≤150

0

NH3/ R-E170

NH3/ R-E170

ammonia/ DME

R404A, R507A, R22

12

-20

-15

-50

0

1

1

B2

22,77

-36,5

-36,5

0

131

110

58

105 (M)

35

MO

PAO

MO/HC

AB

R744

R134a

R404A

R22

≤150

0

CO2

CO2

carbon dioxide

R23, R134a, R404A, R507A

20

-20

-10

-50

0

1

1

1

A1

0,07

44,01

-78,3

-78,3

0

31

73,8

-11

POE

PAG

R744A

>150..750

0

N2O

N2O

nitrous oxide

R23, R508A, R508B

-40

-80

0,017

298

265

273

A1

44,01

-88,5

-88,5

0

36

72,5

-7

special

R1130(E)

0

CClHCClH

HCO

trans-dichloroethene

Chemours

R123

0,0002

5

B2

0,004

96,94

48

48

0

241

48,5

R1132a

≤150

0

CF2CH2

HFO

1,1-difluoro-ethene

Daikin

R23, R508A, R508B

0

1

1

0,052

A2

0,033

64,03

-84

-84

0

30,1

44,33

POE

R1132(E)

≤150

0

E-CFHCFH

HFO

trans-1,2-difluoro-ethene

Daikin

R404A, R507A

0

1

B2

0,028

64,03

-52,5

-52,5

0

75,7

51,7

POE

R1150

≤150

0

CH2CH2

HC

ethylene

R14, R23, R508A, R508B

-50

-100

0

4

4

A3

0,006

28,05

-103,8

-103,8

0

9

50,4

-19

MO

PAO

R1224yd(Z)

≤150

0

(Z)-CF3-CF=CHCl

HCFO

(Z)-1-chloro-2,3,3,3-tetrafluoro-propene

Amolea

R123, R11

80

20

0,00012

4

1

A1

14,6

14,6

0

156

33,3

141

POE

R1233zd(E)

≤150

0

C3H2ClF3

HCFO

trans-1-chloro-3,3,3-trifluoro-1-propene

R123, R11

80

20

0,00034

5

1

3,88

A1

133,5

18,3

18,3

0

166

36,2

147

POE

R1234yf

R134a

≤150

0

CF3FCH2

HFO

2,3,3,3-tetrafluoro-1-propene

Chemours, Honeywell

R134a

25

-25

-30

0

4

1

0,501

A2L

0,058

114,04

-29,5

-29,5

0

95

33,8

82

98 (M)

-14

POE

PVE

R1234ze(E)

R134a

≤150

0

C3H2F4

HFO

trans-1,3,3,3-tetrafluoro-1-propene

Honeywell

R134a

40

-10

0

6

1

1,37

A2L

0,061

114,04

-19

-19

0

109

36,4

92

75 (H)

-6

POE

PVE

R1270

R404A

R22

≤150

0

CH2CHCH3

HC

propylene / propene

R404A, R507A, R22

12

-40

-20

-55

0

2

2

A3

0,008

42,08

-47,6

-47,6

0

91

45,6

61

104 (M)

12

PAO

PAG

POE

AB

MO

R1336mzz(E)

≤150

0

C4H2F6

HFO

trans-1,1,1,4,4,4-hexafluoro-2-butene

R245fa

40

0

0

18

7

17,9

A1

0,048

164,06

7,6

7,6

0

130

27,66

126

POE

special

R1336mzz(Z)

≤150

0

C4H2F6

HFO

cis-1,1,1,4,4,4-hexafluoro-2-butene

R123, R245fa

40

0

0

9

2

2,08

A1

0,087

164,06

33,5

33,5

0

171

29

165

POE

special

MO89

>2500

>0..4

HFC

R125/ 218/ 290

ISCEON MO89

R13B1

-20

-45

-40

-80

0

3805

3324

A1

113,92

-53,2

-50,3

2,9

62

35,6

48

POE

PVE

AB

R401A

>750..2500

>4..8

HCFC

R22/ 152a/ 124

0,04

1182

1130

A1

94,44

-32,9

-27,2

5,7

107,75

46,41

80

101

MO

AB

R401B

>750..2500

>4..8

HCFC

R22/ 152a/ 124

0,04

1288

1240

A1

92,84

-34,6

-29

5,6

106,03

47,25

77

98

MO

AB

R402A

>2500

>0..4

HCFC

R125/ 290/ 22

0,02

2788

2570

A1

101,55

-48,9

-47

1,9

75,07

41,54

53

AB

POE

R402B

>750..2500

>0..4

HCFC

R125/ 290/ 22

0,03

2416

2260

A1

94,71

-47

-44,8

2,2

82,38

44,69

57

77

AB

POE

R403A

>2500

>0..4

HCFC

R290/ 22/ 218

0,04

3124

3100

A1

91,98

-47,4

-44,3

3,1

84,42

44,55

58

79

AB

POE

R403B

>2500

>0..4

HCFC

R290/ 22/ 218

0,03

4457

4460

A1

103,26

-48,6

-46,8

1,8

76,27

39,98

56

AB

POE

R404A

R404A

>2500

>0..4

HFC

R143a/ 125/ 134a

R502, R22

0

-45

7

-30

-70

0

3922

3940

4728

A1

0,52

97,6

-46,2

-45,5

0,7

72

37,35

56

105 (M)

-34

POE

PVE

AB

R407A

R404A

R22

>750..2500

>4..8

HFC

R32/ 125/ 134a

R22, R404A, R507A

0

-40

7

-30

-55

0

2107

1920

2262

A1

0,33

90,11

-45,2

-38,7

6,5

82

44,94

59

98 (M)

-19

POE

PVE

AB

R407B

>2500

>4..8

HFC

R32/ 125/ 134a

0

2804

2550

3001

A1

102,94

-46,5

-42,3

4,2

74,75

41,11

55

POE

R407C

R22

>750..2500

>4..8

HFC

R32/ 125/ 134a

R22, R404A, R507A

12

-25

-30

0

1774

1620

1908

A1

0,31

86,2

-43,8

-36,7

7,1

86

46,15

61

100 (H)

-8

POE

PVE

AB

R407F

R404A

R22

>750..2500

>4..8

HFC

R32/ 125/ 134a

R22, R404A, R507A

0

-40

7

-30

-55

0

1825

1674

1965

A1

0,32

82,06

-46,1

-39,7

6,4

83

47,55

57

104 (M)

-11

POE

PVE

AB

R407H

R404A

R22

>750..2500

>4..8

HFC

R32/ 125/ 134a

R22, R404A, R507A

0

-30

7

-35

0

1490

1380

1615

A1

0,38

79,1

-44,6

-37,6

7

87

48,57

60

99 (M)

-8

POE

PVE

AB

R408A

>2500

>0..4

HCFC

R125/ 143a/ 22

0,03

3152

3260

A1

87,01

-44,6

-44,1

0,5

83,05

42,86

59

AB

POE

R409A

>750..2500

>8

HCFC

R22/ 124/ 142b

0,05

1585

1480

A1

97,43

-34,5

-26

8,5

110,3

47,62

81

102

MO

AB

R409B

>750..2500

>4..8

HCFC

R22/ 124/ 142b

0,05

1560

1470

A1

96,67

-35,6

-27,9

7,7

107,58

47,91

78

99

MO

AB

R410A

R22

R410A

>750..2500

0

HFC

R32/ 125

R22, R13B1

12

-25

-40

-40

-80

0

2088

1920

2256

A1

0,44

72,59

-51,4

-51,4

0

71

49,01

43

140 (H)

-4

POE

PVE

AB

R411A

>750..2500

>0..4

HCFC

R1270/ 22/ 152a

0,05

1597

1560

A2

82,36

-39,5

-36,6

2,9

99,23

49,63

67

88

MO

AB

R411B

>750..2500

>0..4

HCFC

R1270/ 22/ 152a

0,05

1705

1660

A2

83,07

-41,6

-40

1,6

96,04

49,55

64

85

MO

AB

R413A

>750..2500

>4..8

HFC

R218/ 134a/ 600a

0

2053

1950

A1

103,95

-33,4

-28,1

5,3

95,33

39,2

76

AB

POE

R417A

R134a

R22

>750..2500

>4..8

HFC

R125/ 134a/ 600

R22

12

-25

-30

0

2346

2130

A1

0,15

106,75

-39,1

-34,1

5

85

38,94

67

97 (M)

-25

POE

PVE

AB

R417B

R134a

R22

>2500

>0..4

HFC

R125/ 134a/ 600

R22

0

-40

7

0

2920

2740

A1

0,069

113,12

-44,9

-41,5

3,4

74

37,37

58

95 (M)

-37

POE

PVE

AB

R418A

>750..2500

>0..4

HCFC

R290/ 22/ 152a

0,033

1741

1690

A2

84,59

-41,7

-40

1,7

95,98

49,61

64

85

MO

AB

R419A

>2500

>4..8

HFC

R125/ 134a/ E170

0

2967

2690

A2

109,34

-42,6

-35,9

6,7

83,5

40,6

56

POE

R420A

>750..2500

>0..4

HCFC

R134a/ 142b

0,005

1536

1380

A1

101,85

-25

-24,2

0,8

104,76

40,86

83

POE

R421A

>2500

>4..8

HFC

R125/ 134a

0

2631

2380

A1

111,75

-40,7

-35,4

5,3

82,77

39,18

65

POE

R421B

>2500

>0..4

HFC

R125/ 134a

0

3190

2890

A1

116,93

-45,6

-42,4

3,2

72,38

37,46

56

POE

R422A

R22

>2500

>0..4

HFC

R125/ 134a/ 600a

R22

0

-40

7

0

3143

2850

A1

0,29

113,6

-46,5

-44

2,5

71

36,65

55

100 (M)

-39

POE

PVE

AB

R422B

>2500

>4..8

HFC

R125/ 134a/ 600a

0

2526

2290

A1

108,52

-41,3

-35,9

5,4

81,98

38,57

65

POE

R422C

>2500

>0..4

HFC

R125/ 134a/ 600a

0

3085

2790

A1

113,4

-45,9

-42,9

3

72,07

36,96

57

POE

R422D

R22

>2500

>4..8

HFC

R125/ 134a/ 600a

R22

0

-40

7

0

2729

2470

A1

0,26

109,94

-43,2

-38,3

4,9

78

37,95

62

90 (M)

-36

POE

PVE

AB

R427A

R22

>750..2500

>4..8

HFC

R32/ 125/ 143a/ 134a

R22

0

-40

7

0

2138

2020

A1

0,29

90,44

-43

-36,2

6,8

85

44,06

63

90 (M)

-20

POE

PVE

AB

R434A

>2500

>0..4

HFC

R125/ 143a/ 134a/ 600a

0

3245

3080

A1

105,74

-45

-42,3

2,7

74,14

37,32

58

POE

R437A

>750..2500

>0..4

HFC

R125/ 134a/ 600/ 601

R12

12

-30

0

1805

1640

A1

0,081

103,71

-32,4

-28,9

3,5

95

40,03

75

108 (M)

-7

POE

PVE

AB

R438A

R134a

R22

>750..2500

>4..8

HFC

R32/ 125/ 134a/ 600/ 601a

R22

0

-40

7

0

2264

2060

A1

0,079

99,13

-42,3

-35,7

6,6

83

41,79

63

88 (M)

-27

POE

PVE

AB

R442A

>750..2500

>4..8

HFC

R32/ 125/ 134a/ 152a/ 227ea

R404A, R507A

0

-40

0

1888

1750

A1

0,33

81,76

-46,4

-39,7

6,7

82

47,48

57

POE

PVE

R443A

R404A

R22

≤150

>0..4

HC

R1270/ 290/ 600a

0

4

4

A3

43,47

-45,2

-42,1

3,1

96,01

44,85

68

90

PAO

POE

MO

PAG

R444A

R134a

≤150

>8

HFO/ HFC

R32/ 152a/ 1234ze(E)

Klea Edge 444A

Orbia

R134a

25

-20

0

92

89

A2L

0,29

96,7

-35,7

-24,6

11,1

106

44,73

81

POE

PVE

R444B

R22

>150..750

>8

HFO/HFC

R32/ 152a/ 1234ze(E)

L-20

Honeywell

R407C, R22

12

-35

0

295

295

A2L

0,055

72,76

-45

-35

10

92

52,1

POE

PVE

R447B

R410A

>150..750

>0..4

HFO/HFC

R32/ 125/ 1234ze(E)

L-41z

Honeywell

R410A

15

-25

0

740

714

A2L

-50

-46

4

84

49

68

POE

PVE

R448A

R404A

>750..2500

>4..8

HFO/ HFC

R32/ 125/ 1234yf/ 1234ze(E)/ 134a

N-40

Honeywell

R404A, R507A

12

-40

-45

-25

-65

0

1387

1273

1494

A1

0,388

86,28

-46,1

-39,9

6,2

83

45,95

58

96 (M)

12

POE

PVE

R449A

R404A

>750..2500

>4..8

HFO/ HFC

R32/ 125/ 1234yf/ 134a

XP40, 449A

Chemours, Arkema

R404A, R507A

12

-40

-45

-25

-65

0

1397

1282

1504

A1

0,357

87,21

-45,7

-40

5,7

82

45

58

77

96 (M)

12

POE

PVE

R449B

R404A

>750..2500

>4..8

HFO/HFC

R32/ 125/ 1234yf/ 134a

Arkema

R404A, R507A

12

-40

-25

-65

0

1412

1296

A1

-46

-40

6

84

44,3

POE

PVE

R449C

R22

>750..2500

>4..8

HFO/ HFC

R32/ 125/ 1234yf/ 134a

Chemours

R407C, R22

12

-35

0

1251

1146

A1

0,362

-44

-38

6

84

61

81

POE

PVE

R450A

R134a

>150..750

>0..4

HFO/ HFC

R1234ze(E)/ 134a

N-13

Honeywell

R134a, R12

25

-25

0

604

547

643

A1

0,319

108,67

-23,4

-22,8

0,6

104

38,2

86

88 (M)

-6

POE

PVE

R452A

R404A

>750..2500

>0..4

HFO/ HFC

R32/ 125/ 1234yf

XP44

Chemours

R404A, R507A

12

-40

-25

-65

0

2140

1945

2292

A1

0,423

103,51

-46,9

-43,1

3,8

75

40,03

56

75

POE

PVE

R452B

R404A

R410A

>150..750

>0..4

HFO/ HFC

R32/ 125/ 1234yf

XL55, L-41y

Chemours, Honeywell

R410A

15

-25

0

698

676

779

A2L

0,062

63,53

-50,7

-49,8

0,9

77

52,2

46

65

98 (H)

7

POE

PVE

R452C

R404A

>750..2500

>0..4

HFO/HFC

R32/ 125/ 1234yf

Arkema

R404A, R507A

12

-40

-25

-65

0

2220

2019

A1

0,43

101,95

-47,5

-44,1

3,4

74

40,55

52

73

POE

PVE

R454A

R404A

>150..750

>4..8

HFO/ HFC

R32/ 1234yf

XL40, ARM-20b

Chemours, Arkema

R404A, R507A

12

-40

-25

-65

0

239

238

270

A2L

0,056

79,79

-47,9

-42,2

5,7

82

46,3

57

76

POE

PVE

R454B

R410A

>150..750

>0..4

HFO/ HFC

R32/ 1234yf

XL41

Chemours

R410A

15

-25

0

466

467

531

A2L

0,061

62,61

-50,5

-49,5

1

78

52,67

47

66

97 (H)

0

POE

PVE

R454C

R404A

≤150

>4..8

HFO/ HFC

R32/ 1234yf

XL20

Chemours

R404A, R507A

12

-40

-25

-65

0

148

146

166

A2L

0,059

90,78

-45,6

-37,8

7,8

86

43,2

64

83

POE

PVE

R455A

R404A

≤150

>8

HFO/ HFC

R32/ 1234yf/ 744

L-40X

Honeywell

R404A, R507A

12

-40

-25

-65

0

148

146

166

A2L

0,105

87,45

-52

-39,2

12,8

86

46,5

61

93 (M)

10

POE

PVE

R456A

R134a

>150..750

>4..8

HFO/ HFC

R32/ 1234ze(E)/ 134a

Klea 456A

Orbia

R134a

10

-20

0

687

627

A1

0,32

104,9

-30,4

-25,6

4,8

102,4

41,75

80

POE

PVE

R457A

R404A

≤150

>4..8

HFO/ HFC

R32/ 1234yf/ 152a

ARM-20a

Arkema

R404A, R507A

12

-40

-25

-65

0

139

139

A2L

0,043

87,61

-42,6

-35,5

7,1

90

43,08

68

85

POE

PVE

R457B

R404A

>150..750

>4..8

HFO/HFC

R32/ 1234yf/ 152a

ARM-20b

Arkema

R404A, R507A

7

-45

0

276

279

319

A2L

76,5

-46,4

-40,4

6

POE

PVE

R457C

R404A

≤150

>4..8

HFO/HFC

R32/ 1234yf/ 152a

Chemours

R134a

12

-35

0

72

72

82

A2L

0,054

95,4

-37,3

-32,1

5,2

94,1

39,6

POE

PVE

R459A

R410A

>150..750

>0..4

HFO/HFC

R32/ 1234yf/ 1234ze(E)

ARM-71a

Arkema

R410A

15

-25

0

460

461

A2L

0,056

62,98

-50,3

-48,5

1,8

80

53,4

46

65

POE

PVE

R459B

R404A

≤150

>8

HFO/HFC

R32/ 1234yf/ 1234ze(E)

Klea Edge 459B

Orbia

R404A, R507A

7

-35

0

144

143

A2L

0,48

91,21

-45

-36,7

8,3

87

43,61

66

POE

PVE

R460A

R404A

>750..2500

>4..8

HFO/HFC

R32/ 1234ze(E)/ R134a

Klea 460A

Orbia

R404A, R507A

7

-35

0

2103

1911

A1

0,38

100,6

-44,6

-36,6

8

84

43,36

61

POE

PVE

R460B

R404A

>750..2500

>8

HFO/HFC

R32/ 1234ze(E)/ R134a

Klea 460B

Orbia

R404A, R507A

7

-35

0

1352

1242

A1

0,399

84,8

-45,6

-36,9

8,7

88

48,9

60

POE

PVE

R463A

>750..2500

>8

HFO/ HFC

R32/ 125/ 1234yf/ 134a/ 744

XP41

Chemours

R410A

15

-25

0

1494

1377

A1

0,299

74,72

-59,9

-46,9

13

76

52,44

47

65

POE

PVE

((nicht kommerzialisiert)R465A

R404A

≤150

>8

HFO/ HFC

R32/ 1234yf/ 290

ARM-25

Arkema

R404A, R507A

7

-40

0

145

143

162

A2

0,04

82,9

-51,7

-40

11,7

82

43,36

60

POE

PVE

R466A

R410A

>150..750

>0..4

HFO/ HFC

R32/ 125/ 13I1

N-41

Honeywell

R410A

15

-25

0

733

696

A1

0,099

80,69

-51,7

-51

0,7

76

51,44

46

65

POE

PVE

R468A

R404A

≤150

>8

HFO/ HFC

R32/ 1234yf/ 1132a

Daikin Chemical

R404A, R507A, R22

0

-40

0

148

147

166

A2L

88,8

-51,2

-39

12,2

84

44,54

62

POE

R468B

R410A

≤150

>8

HFO/HFC

R32/ 1234yf/ 1132a

Orbia

R410A, R404A, R507A

0

-40

0

101

A2L

0,07

94,9

-52,4

-36,8

15,6

85

42,5

POE

R468C

R410A

>150..750

>8

HFO/HFC

R32/ 1234yf/ 1132a

Orbia

R410A

15

-25

0

324

A2L

0,069

73,7

-56,6

-46,2

10,4

76,8

48,9

POE

R469A

>750..2500

>8

HFC/ CO2

R744/ 32/ 125

WT69

TEGA

R23

-40

-75

0

1358

1250

1621

A1

59,1

-78,5

-61,5

17

59

65,17

23

POE

R471A

R134a

≤150

>0..4

HFO/ HFC

R1234ze(E)/ 1336mzz(E)/ 227ea

Honeywell

(R134a)

20

-20

0

148

148

148

A1

122,09

-16,9

-13,7

3,2

112

35,34

97

67 (H)

-7

POE

R472A

>150..750

>8

HFC/CO2

R744/ 32/ 134a

Angeletoni

R23

0

353

329

384

A1

0,072

50,39

-84,3

-61,5

22,8

50,2

77,5

POE

R472B

>150..750

>8

HFC/CO2

R744/ 32/ 134a

Angeletoni

R23

0

526

484

567

A1

0,08

54,8

-82,9

-54,8

28,1

57,9

77,1

POE

R473A

>750..2500

>0..4

HFO/HFC

R744/ 1132a/ 23/ 125

Klea 473A

Orbia

R23

-40

-80

0

1830

1558

1835

A1

0,077

52,58

-87,6

-83

4,6

29,72

62,87

-5

11

POE

PVE

R474A

R134a

≤150

>4..8

HFO

R1132(E)/ 1234yf

Daikin

R134a

10

-35

0

2

A2L

0,053

96,7

-43,1

-36,4

6,7

87,1

40,4

POE

R475A

R134a

>150..750

>0..4

HFO/HFC

R134a/ 1234yf/ 1234ze(E)

Gree

R134a

15

-30

0

619

560

659

A1

0,32

108,54

-28,8

-28,3

0,5

99,3

37,2

POE

R476A

R134a

≤150

>0..4

HFO/HFC

R134a/ 1234ze(E)/ 1336mzz(E)

Honeywell

R134a

25

-15

0

132

156

A1

0,18

116,9

-19,1

-16,1

3

110

36,3

POE

R500

>2500

0

CFC

R12/ 152a

10

-30

0,74

8077

7560

A1

0,4

99,3

-33,6

-33,6

0

102

41,68

78

MO

AB

R502

R404A

>2500

0

CFC

R22/ 115

10

-50

0,33

4657

4790

A1

0,45

111,64

-45,4

-45,4

0

82

40,7

60

AB

R503

>2500

0

CFC

R13/ 23

-50

-90

0,6

14560

13300

A1

0,35

87,24

-87,9

-87,9

0

20

43,43

-2

AB

R507A

R404A

>2500

0

HFC

R143a/ 125

R502, R22

0

-45

7

-30

-70

0

3985

3990

4775

A1

0,53

98,86

-46,7

-46,7

0

71

37,05

54

107 (M)

-34

POE

PVE

AB

R508A

>2500

0

HFC

R23/ 116

R503

-50

-95

0

13210

11600

A1

0,23

100,1

-87,6

-87,6

0

10

36,48

-3

POE

R508B

>2500

0

HFC

R23/ 116

R503

-50

-95

0

13400

11700

A1

0,25

95,39

-87,6

-87,6

0

11

37,71

-3

POE

R511A

≤150

0

HC

R290/ E170

0

3

3

A3

44,19

-42

-42

0

96,98

42,88

70

PAO

POE

MO

R513A

R134a

>150..750

>0..4

HFO/ HFC

R1234yf/ 134a

XP10

Chemours

R134a, R12, R404A

25

-25

-30

0

631

573

673

A1

0,319

108,31

-29,6

-29,5

0,1

95

36,5

78

102 (M)

-7

POE

PVE

R513B

R134a

>150..750

0

HFO/HFC

R1234yf/ 134a

Daikin Chemical

R134a

25

-25

0

596

540

895

A1

108,73

-29,6

-29,6

0

95

36,32

79

POE

PVE

R514A

≤150

0

HFO

R1336mzz(Z)/ 1130(E)

XP30

Chemours

R11, R123, (R134a)

40

0

0

7

2

B1

0,013

139,6

28,8

28,8

0

178

34,7

161

POE

R515B

R134a

>150..750

0

HFO/ HFC

R1234ze(E)/ 227ea

N-15

Honeywell

R134a

20

-20

0

293

299

322

A1

0,29

117,48

-18,8

-18,8

0

109

35,84

93

75 (H)

-7

POE

R516A

R134a

≤150

0

HFO/ HFC

R1234yf/ 152a/ 134a

ARM-42

Arkema

R134a

25

-25

0

142

131

153

A2L

0,042

102,58

-29,4

-29,4

0

97

36,23

80

POE